Stove Installation
Insert Placement Requirements
•
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
•
Insert and hearth must be installed on a level, secure floor
•
The minimum clearances, facing, and hearth requirements in Figure 3 must be met (follow the
clearances for the type of fireplace being used - either masonry or zero-clearance).
Side
Wall
k
l
p
q
Hearth Requirements
•
Must extend 16" in front of the insert and 8" on both sides (min. 26" deep by 40-1/4" wide)
•
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
•
Chimney must have a clay tile liner or a stainless steel liner (positive connection)
•
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert
•
Chimney height: 15' minimum; 33' maximum.
•
Entire fireplace, including chimney, must meet local building requirements
© Travis Industries
n
m
x
o
(for qualified installers only)
Minimum Clearances
k
Sidewall to Insert
l
Side Facing
m
Top Facing
with mantel shield
n
Mantel to Insert
with mantel shield
o
Hearth (Front)
p
Hearth (Side)
q
Front of Insert
x
Extension onto Hearth
100-01165
9
Masonry
ZC (Metal)
Fireplace
Fireplace
15"
30"
13"
12"
28-1/2"
12"
20-1/2"
N/A
30-1/2"
24"
22-1/2"
N/A
16"
16"
8"
8"
36"
36"
10"
10"