Consider two primary elements when connecting your
stove to a masonry chimney: the chimney itself and the
thimble where the stovepipe connects to the chimney.
Use only Code approved masonry chimneys with a flue
liner.
Before connecting to a masonry chimney, hire a
professional to examine the chimney for cracks, loose
mortar, and other signs of deterioration and blockage. If
the chimney needs repair, complete them before installing
and using your stove. Do not install your stove until the
chimney is safe for use.
Make sure the chimney's cleanout is complete and
working properly. To avoid a loss of draft, the cleanout
must close off completely. If not, the chimney will cool,
your stove will perform poorly, and creosote will build up
in the chimney.
Make sure the size of the chimney's flue is appropriate for
this stove and that it is not too large. Use a masonry
chimney with an 8" x 8" (203 mm x 203 mm) tile size for
best results. An oversized flue will contribute to the
accumulation of creosote.
Minimum Requirements:
At least 3' (0.91 m) higher than highest part of roof
opening through which it passes and at least 2' (0.61 m)
higher than any part of the roof within 10' (3 m).
Use the following checklist to ensure that your masonry
chimney meets these minimum requirements:
Chimney wall construction:
q
Brick or modular block at least 4" (102 mm) thick.
q
A rubble or stone wall at least 12" (305mm) thick.
Flue liner:
q
Minimum thickness of 5/8" (16 mm).
q
Installed with refractory mortar.
q
At least 1" (25 mm) air space.
q
An equivalent flue liner must be a listed chimney
liner system meeting type HT requirements or other
approved material.
Interior chimney requirements:
q
At least 2" (51 mm) clearance to combustible
structure
HearthStone Quality Home Heating Products Inc ®
C
ASONRY
HIMNEY
q
Fire stops must be installed at the spaces where the
chimney passes through floors and/or ceiling.
q
Insulation must be 2" (51 mm) from the chimney.
Exterior chimney requirements:
q
At least 1" (25 mm) clearance to combustible
structure.
Chimney height requirements for both prefabricated metal
and masonry chimneys: (See Illustration)
q
At least 3 feet (0.9 m) higher than the highest part of
the roof opening through which it passes.
q
At least 2 feet (0.6 m) higher than any part of the roof
within 10 feet (3 m) measured horizontally from the
top of the chimney.
This stove requires a minimum chimney height of 13 feet
(4 m). The maximum allowable chimney height is 30 feet
(9m).