Connection T O A Masonry Chimney - HearthStone Phoenix 8612 Owner's Manual

Non-catalytic wood stove
Hide thumbs Also See for Phoenix 8612:
Table of Contents

Advertisement

C
T
ONNECTION
O
Consider
two
primary
connecting your stove to a masonry chimney:
the chimney itself and the thimble where the
stovepipe connects to the chimney. Use only
Code approved masonry chimneys with a flue
liner.
Before connecting to a masonry chimney, hire a
professional to examine the chimney for cracks,
loose mortar, other signs of deterioration, and
blockage. If the chimney needs repairs,
complete them before installing and using your
stove.
Do not install your stove until the
chimney is pronounced safe for use.
Make sure the chimney's cleanout is complete
and working properly. To avoid a loss of draft,
ensure the cleanout closes tightly.
Make sure the size of the chimney's flue is
appropriate for this stove, and that it is not too
large. Use a masonry chimney with an 8" x 8"
(203 mm x 203 mm) maximum tile size for best
results. An oversized flue will contribute to the
accumulation of creosote.
Use the following checklist to ensure that your
masonry
chimney
requirements:
Chimney wall construction:
Brick or modular block at least 4" (102
mm) thick.
A mortared rubble or stone wall.
HearthStone Quality Home Heating Products Inc ®
A M
C
ASONRY
HIMNEY
elements
meets
these
minimum
Flue liner:
Minimum thickness of 5/8" (16 mm).
when
Installed with refractory mortar.
At least 1" (25 mm) air space.
An equivalent flue liner must be a listed
chimney liner system meeting type HT
requirements or other approved material.
Interior chimney requirements:
At least 2" (51 mm) clearance to
combustible structure.
Fire stops installed at the spaces where
the chimney passes through floors and/or
ceiling.
2" (51 mm) gap maintained to any
insulation from the chimney.
Exterior chimney requirements:
At least 1" (25 mm) clearance to
combustible structure.
Chimney
Illustration)
At least 3 feet (0.9 m) higher than the
highest part of the roof opening through
which it passes.
At least 2 feet (0.6 m) higher than any
part of the roof within 10 feet (3 m)
measured horizontally from the top of the
chimney.
This stove requires a minimum chimney height
of 13 feet (4 m).
chimney
17
height
requirements:
The maximum allowable
height
is
30
(See
feet
(9m).
Phoenix Model 8612