Consider two primary elements when connecting
your stove to a masonry chimney: the chimney itself
and the thimble where the stovepipe connects to the
chimney.
Use only Code approved masonry
chimneys with a flue liner.
Before connecting to a masonry chimney, hire a
professional to examine the chimney for cracks,
loose mortar, other signs of deterioration, and
blockage. If the chimney needs repairs, complete
them before installing and using your stove. Do not
install your stove until the chimney is pronounced
safe for use.
Make sure the chimney's cleanout is complete and
working properly. To avoid a loss of draft, ensure the
cleanout closes tightly.
Make sure the size of the chimney's flue is
appropriate for this stove, and that it is not too large.
Use a masonry chimney with an 8" x 8" (203 mm x
203 mm) maximum tile size for best results.
oversized flue will contribute to the accumulation of
creosote.
Use the following checklist to ensure that your
masonry
chimney
requirements:
C
ASONRY
HIMNEY
meets
these
minimum
Hearthstone Quality Home Heating Products, Inc ®
www.hearthstonestoves.com
Chimney wall construction:
Brick or modular block at least 4" (102 mm) thick.
A mortared rubble or stone wall.
Flue liner:
Minimum thickness of 5/8" (16 mm).
Installed with refractory mortar.
At least 1" (25 mm) air space.
An equivalent flue liner must be a listed chimney
liner system meeting type HT requirements or
other approved material.
Interior chimney requirements:
1. At least 2" (51 mm) clearance to combustible
structure.
2. Fire stops installed at the spaces where the
chimney passes through floors and/or ceiling.
3. 2" (51 mm) gap maintained to any insulation
from the chimney.
Exterior chimney requirements:
1. At least 1" (25 mm) clearance to combustible
structure.
Chimney
height
below)
An
1. At least 3 feet (0.9 m) higher than the highest
part of the roof opening through which it
passes.
2. At least 2 feet (0.6 m) higher than any part of
the roof within 10 feet (3 m) measured
horizontally from the top of the chimney.
This stove requires a minimum chimney height of 13
feet (4 m). The maximum allowable chimney height
is 30 feet (9m).
Phoenix Model 8612
requirements:
(See
Figure
16