Make Electrical Connections

Field wiring must be installed in accordance with job wiring diagrams and all applicable
electrical codes.
CAUTION
Do not run 120-v wiring into the control center. The control center should only be
used for additional extra low-voltage wiring (50 v maximum).
Wiring information in this publication
Figure
20,
Figure
21,
are not intended for use during actual installation; follow job specific wiring diagrams.
WARNING
Do not attempt to start compressor or oil pump (even for a rotation check) or
apply test voltage of any kind while machine is under dehydration vacuum. Motor
insulation breakdown and serious damage may result.
!
CAUTION
(Figure
Figure
22,
Figure
23,
!
WARNING
15,
Figure
16,
Figure
Figure 24
and
Figure
17,
Figure
18,
Figure
25) are for reference only and
19,