Carrier EVERGREEN HFC-134A Installation Instructions Manual
Carrier EVERGREEN HFC-134A Installation Instructions Manual

Carrier EVERGREEN HFC-134A Installation Instructions Manual

High-efficiency variable speed screw chiller with foxfire compression technology and pic iii controls 50/60 hz hfc-134a

Advertisement

Screw liquid chillers are designed to provide safe and
reliable service when operated within design specifica-
tions. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to
equipment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the machine instruc-
tions, as well as those listed in this guide.
DO NOT VENT refrigerant relief devices within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accor-
dance with the latest edition of ANSI/ASHRAE 15 (American
National Standards Institute/American Society of Heating, Refrigera-
tion and Air-Conditioning Engineers) (Safety Code for Mechanical
Refrigeration). The accumulation of refrigerant in an enclosed space
can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead spaces.
Inhalation of high concentrations of vapor is harmful and may cause
heart irregularities, unconsciousness, or death. Intentional misuse can
be fatal. Vapor is heavier than air and reduces the amount of oxygen
available for breathing. Product causes eye and skin irritation.
Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a machine
for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.
NEVER EXCEED specified test pressures. VERIFY the allowable
test pressure by checking the instruction literature and the design
pressures on the equipment nameplate.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any machine.
RISK OF INJURY OR DEATH by electrocution. High voltage
is present on motor leads even though the motor is not running.
Open the power supply disconnect before touching motor leads or
terminals.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and the
work area should be well ventilated. Refrigerant in contact with an
open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig heat exchangers or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control
panels, switches, starters, or oil heater until you are sure ALL
POWER IS OFF and no residual voltage can leak from capacitors or
solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY
FLUSH EYES with water and consult a physician.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 532-309
Book 2
Tab
5e
23XRV High-Efficiency Variable Speed Screw Chiller

Installation Instructions

SAFETY CONSIDERATIONS

Printed in U.S.A.
with Foxfire™ Compression Technology
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar, and
unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the machine. The introduction of the wrong refrigerant can cause
machine damage or malfunction.
Operation of this equipment with refrigerants other than those
cited herein should comply with ANSI/ASHRAE 15 (latest edition).
Contact Carrier for further information on use of this machine with
other refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
machine is under pressure or while machine is running. Be sure pres-
sure is at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If machine operates in a
corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
valve when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the valve.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a machine. Use platform, catwalk, or staging.
Follow safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if compo-
nents are light, use mechanical equipment when there is a risk of
slipping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fan, and pumps. Shut off the
machine or pump before servicing equipment.
USE only repaired or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or
other items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
Form 23XRV-1SI
Pg 1
EVERGREEN®
and PIC III Controls
50/60 Hz
HFC-134a
309
6-06
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVERGREEN HFC-134A and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier EVERGREEN HFC-134A

  • Page 1: Installation Instructions

    Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for further information on use of this machine with other refrigerants. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while machine is under pressure or while machine is running.
  • Page 2: Table Of Contents

    Connect Control Wiring ......43 Carrier Comfort Network Interface....43 Lead-Lag Control Wiring .
  • Page 3: Rigging The Machine

    [National Electric Code]/CEC [California Energy Commis- sion] regulations). General recommendations are included in the Carrier field wiring drawing. Conduit Entry Size — It is important to determine the size of the conduit openings in the enclosure power entry plate so that the wire planned for a specific entry point will fit through the opening.
  • Page 4 a23-1548 35 34 32 31 a23-1549 a23-1550 Fig. 3 — Typical 23XRV Components 1 — Motor Terminal Cover Plate 2 — Variable Frequency Drive 3 — International Chiller Visual Controller (ICVC) 4 — Discharge Pipe Relief Valve 5 — Condenser 6 —...
  • Page 5 a23-1551 12 13 a23-1552 Fig. 4 — Typical 23XRV Installation (Sensor Locations) a23-1553 1 — Condenser Pressure 2 — Evaporator Pressure 3 — Compressor Discharge Temperature 4 — Compressor Discharge Pressure 5 — Compressor Discharge High Pressure Switch 6 — Compressor Motor Winding Temperature (Hidden) 7 —...
  • Page 6 a23-1554...
  • Page 7: Machine Rigging Guide

    Fig. 7 — Machine Electrical Data Nameplate HEAT EXHANGER COMPRESSOR CODE FRAME SIZE* 30-32 35-37 40-42 45-47 50-52 55-57 *The 11th character of the chiller model number indicates the frame size of the compressor. CHAIN “B” (SEE NOTE #2) CHAIN “C” (SEE NOTE #2) “E”...
  • Page 8 Fig. 9 — 23XRV Dimensions (Refer to Tables 2 and 3) Table 1 — Drive Assembly and Power Module Ratings CARRIER PART NUMBER 23XRA2AA_ _ _ _ _ _ _ _ _ _ _ 23XRA2BA_ _ _ _ _ _ _ _ _ _ _...
  • Page 9 Table 3 — 23XRV Dimensions (Marine Waterbox) A (Length, Marine Waterbox — not shown) HEAT EXCHANGER 2-Pass* SIZE ft-in. 30 to 32 14- 9 35 to 37 16- 5 40 to 42 15- 2 45 to 47 16-11 50 to 52 15- 3 55 to 57 17- 0...
  • Page 10 ENGLISH Dry Rigging Weight (lb)* CODE Refrigerant Weight (lb) Cooler Condenser Only Only With Economizer 4148 3617 4330 3818 4522 4023 4419 4529 4627 4758 4845 4992 5008 4962 5178 5155 5326 5347 5463 5525 1015 5659 5747 1015 5830 5967 1015 5827...
  • Page 11: Rig Machine Components

    NOTE: Weight for NIH 2-pass cover, 150 psig (1034 kPa), is included in the heat exchanger weights shown in Table 7. RIG MACHINE COMPONENTS — Refer to Fig. 10-26 and Carrier Certified Prints for machine component disassembly. IMPORTANT: Only a qualified service technician should perform this operation.
  • Page 12 WATER SENSOR CABLES FOR NOZZLE ARRANGEMENTS A,B,C,E,F,P,Q,R,T,&U (SAME FOR OTHER END OF MACHINE) DISCHARGE END DISCH. TEMP. CABLE DISCH. PRESS. CABLE DISCH. PRESS. SWITCH a23-1558 Fig. 10 — Electrical Cable Routing (Top View) CABLE TRAY CONTAINING OIL VAPORIZER CONDUIT OIL HTR CONDUIT OIL PUMP CONDUIT OIL RECLAIM ACTUATOR CABLE OIL SUMP PRESS.
  • Page 13: Separate Machine Components

    Separate Machine Components — the 23XRV allows for disassembly at the job site so that individual components may be moved through existing door- ways. Use the following procedures to separate the machine components. Suggested locations to cut piping will minimize the width of the condenser/economizer assembly.
  • Page 14: From The Condenser

    9. Cut the vaporizer refrigerant return line as shown. 10. Disconnect all sensors with cables that cross from the condenser side of the machine to the cooler side including: a. Evaporator refrigerant liquid temperature sensor. See Fig. 13. b. Entering and leaving chiller liquid temperature sensors.
  • Page 15: Condenser

    SHIPPING BRACKET Fig. 16 — VFD Shipping Bracket 3. Remove the nuts that secure the terminal box transition piece to the motor housing. 4. Disconnect the motor leads from the motor terminals (Fig. 17). Note the position of the motor terminal cable lugs so they can be reinstalled with sufficient clearance away from surrounding structure.
  • Page 16: Remove The Discharge Pipe Assembly From The Condenser

    OIL HEATER CONDUIT ASY OIL PUMP CONDUIT ASY VAPORIZER HEATER CONDUIT ASY VFD COOLING LINE O-RING FACE SEAL COUPLINGS OIL RECLAIM ACTUATOR CABLE VFD COOLING SOLENOID CABLE TEMPERATURE SENSOR CABLES PRESSURE SENSOR CABLES a23-1571 Fig. 20 — Control Panel Back Lifting the Control Center —...
  • Page 17: Separate The Compressor From The Condenser

    SEPARATE COMPRESSOR CONDENSER Do not rig the condenser before the control center and compressor are removed. The condenser/compressor assembly has a high center of gravity and may tip over when lifted at the tubesheet rigging points, which could result in equipment damage and/or serious personal injury. TO TERMINAL J4-10 UPPER Fig.
  • Page 18: Condenser

    Table 10 — Compressor Fastener Identification COMPRESSOR FASTENERS Discharge Pipe Assembly to 1 in.-8 Grade 5 Hex Head Compressor Discharge Flange Suction Elbow to Compressor Inlet in.-9 Grade 5 Hex Head Compressor Mount to Condenser Economizer Line in.-11 Grade 8 Hex Head Motor Cooling, Motor Drain, Oil Drain M 12x1.75 Grade 10.9 Socket Head Compressor Lifting Points (2)
  • Page 19: Separate The Vaporizer From The

    5. Check all terminal connections for proper installation. IMPORTANT: Do not insulate terminals until wiring arrangement has been checked and approved by Carrier start-up personnel. Motor terminals must be insulated in acceptance with national and local electri- cal codes. VFD MOUNTING...
  • Page 20 OIL SUPPLY LINE VAPORIZER OIL PUMP OIL FILTER VAPORIZER HOT GAS RETURN a23-1574 LINE OIL FILTER SCHRADER VALVE VAPORIZER REFRIGERANT RETURN ORIFICE OIL SUMP STRAINER OIL PUMP/OIL FILTER a23-1575 ISOLATION VALVE Fig. 26 — Oil Reclaim Components BEARING OIL DRAIN LINE OIL PRESSURE REGULATOR VALVE OIL SUMP...
  • Page 21 MOTOR TEMPERATURE SENSOR TERMINAL BLOCK THERMAL INSULATOR COMPRESSOR FOAM INSULATION TERMINAL BOX MOUNTING STUD - DO NOT EXCEED a23-1576 SECTION E-E 120 FT-LB TORQUE TERMINAL ENCLOSURE FRAME WASHER MOTOR TERMINAL STUD NUTS SECTION C-C FROM FIG. 27 INTERNAL/EXTERNAL TOOTH LOCK WASHER BETWEEN TERMINAL BOX FRAME AND a23-1577...
  • Page 22: Install Standard Isolation

    Ends — Insulate compressor motor terminals, lead wire ends, and electrical wires to prevent moisture condensa- tion and electrical arcing. Obtain Carrier approved insula- tion material from RCD (Replacement Components Division) consisting of 3 rolls of insulation putty and one roll of vinyl tape.
  • Page 23: Install Accessory Isolation

    INSTALL ACCESSORY ISOLATION (if required) — Un- even floors or other considerations may dictate the use of accessory soleplates (supplied by Carrier for field installation) and leveling pads. Refer to Fig. 33. Level machine by using jacking screws in isolation sole- plates.
  • Page 24: Install Spring Isolation

    Spring isolation may be purchased as an accessory from Carrier for field installation. It may also be field supplied and installed. Spring isolators may be placed directly under machine support plates or located under machine soleplates.
  • Page 25 a23-1538 CONDENSER a23-1581 DISCHARGE END NOZZLE ARRANGEMENT CODES FOR ALL 23XRV NOZZLE-IN-HEAD WATERBOXES COOLER WATERBOXES PASS *Refer to certified drawings. Fig. 36 — Piping Flow Data (NIH, Frames 3 Through 5) NOZZLE-IN HEAD WATERBOXES FRAME 3 COOLER FRAMES 4 AND 5 PASS Arrangement Code*...
  • Page 26: Marine Waterboxes

    a23-1539 COOLER WATERBOXES PASS Fig. 17 — Piping Flow Data (MWB, Frames 2 and 3) a23-1540 COOLER WATERBOXES PASS Fig. 37 — Piping Flow Data (Marine Waterboxes, Frames 3 Through 5) MARINE WATERBOXES FRAME 3 NOZZLE ARRANGEMENT CODES Arrangement Code —...
  • Page 27: Top View

    LEVEL GAGE 0' - 5 1/2" [140mm] PRESSURE GAGE a23-1541 1/2" MALE FLARE VAPOR CONN. 3/4" NPT PUMPOUT CONDENSER WATER INLET CONN. NOTES: Denotes center of gravity. 2. Dimensions in [ ] are in millimeters. 3. The weights and center of gravity values given are for an empty storage tank.
  • Page 28 RATED DRY WEIGHT AND REFRIGERANT CAPACITY TANK TANK OD SIZE (in.) 0428 24.00 0452 27.25 TANK TANK OD SIZE (mm) 0428 0452 LEGEND ANSI — American National Standard Institute ASHRAE — American Society of Heating, Refrigeration, and Air Conditioning Engineers —...
  • Page 29 COOLER INLET ISOLATION VALVE COOLER CONTROL CENTER DISCHARGE ISOLATION VALVE (OPTIONAL) SERVICE VALVE ON PUMPOUT UNIT = MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND STORAGE TANK FOR SERVICE AND OPERATION WORK. a23-1544 Fig. 40 — Optional Pumpout System Piping Schematic with Storage Tank (Configured to Pull Vapor out of Chiller or to Charge Chiller from Storage Tank) COOLER INLET ISOLATION VALVE...
  • Page 30: Install Vent Piping To Relief Valves

    FRAME ASSEMBLY CONTROL PANEL VALVE VALVE VALVE VALVE ENTERING WATER SEPARATOR LEAVING a23-1546 CONDENSER WATER Fig. 42 — Pumpout Unit INSTALL VENT PIPING TO RELIEF VALVES — The 23XRV chiller is factory equipped with relief valves on the cooler and condenser shells. Refer to Fig. 43 and Table 11 for size and location of relief devices.
  • Page 31: Grounding The Controls/Drive Enclosure

    AC drives. Any questions or problems with the products described in this man- ual should be directed to your local Carrier Service Office. Wiring diagrams in this publication are for reference only and are not intended for use during actual installation; follow job specific wiring diagrams.
  • Page 32 a23-1585 Fig. 44 — Typical Field Wiring Schematic...
  • Page 33 a23-1586 Fig. 44 — Typical Field Wiring Schematic (cont)
  • Page 34 Fig. 44 — Typical Field Wiring Schematic (cont)
  • Page 35 Ice build start/terminate device contacts, remote start/stop device contacts and spare safety device contacts, (devices not supplied by Carrier), must have 24 VAC rating. Max cur- rent is 60 mA, nominal current is 10 mA. Switches with gold plated bifurcated contacts are recommended.
  • Page 36 a23-1584...
  • Page 37: Enclosure

    Additional spare sen- sors and Carrier Comfort Network® modules may be specified as well. These are wired to the machine control panel as indicated in Fig.
  • Page 38 a23-1588 Fig. 46 — 23XRV Controls Schematic...
  • Page 39 a23-1589 Fig. 46 — 23XRV Controls Schematic (cont)
  • Page 40 a23-1591 a23-1590 Fig. 47 — Control Terminal Blocks DPI Communications Interface Board Status LEDs a23-1592 Fig. 48 — Communications Interface Board Status Lights...
  • Page 41 a23-1593...
  • Page 42 Certified field wiring and dimensional diagrams are avail- able on request. NOTES: 1. All wiring must comply with applicable codes. 2. Refer to Carrier System Design Manual for details regarding piping techniques. 3. Wiring not shown for optional devices such as: • remote start-stop •...
  • Page 43: Completing The Installation

    This section provides instructions on how to perform a final check of the installation. Do not energize the VFD circuit breaker. This should only be done by qualified Carrier person- nel in accordance with the 23XRV Start-Up and Service Manual.
  • Page 44: Lead-Lag Control Wiring

    When connecting the CCN communication bus to a system element, a color code system for the entire network is recom- mended to simplify installation and checkout. See Table 14 for the recommended color codes: Table 14 — Insulator Codes CCN BUS CONDUCTOR SIGNAL TYPE INSULATION...
  • Page 45 a23-1597...
  • Page 46 a23-1598...
  • Page 47 a23-1599...
  • Page 50 Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 532-309 Printed in U.S.A. Form 23XRV-1SI Pg 50 6-06 Replaces: New Book 2...
  • Page 51: Checklist

    Project Name Carrier Job Number The following information provides the status of the chiller installation. Send a copy of this checklist to the local Carrier Service office after it has been completed and signed-off by the Purchaser and Job Site Supervisor.
  • Page 52 Concerns about the installation/request for additional assistance: I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the machine and the options and accessories used with it.

This manual is also suitable for:

Evergreen 23xrvEvergreen 23xrv series

Table of Contents

Save PDF