Table 1A — Rigging and Operating Weights — English (lb)
Steel Base (includes Storage Tank)
Legend
MWB — Marine Waterbox
NIH
— Nozzle-In-Head Waterbox
*Based on 2 pass NIH waterboxes. If 2 pass MWB are used, add an additional 2,250 lb (1021 kg).
†Based on 2 pass NIH waterboxes. If 2 pass MWB are used, add an additional 2,100 lb (953 kg).
Heat Exchanger Combinations
Condenser
Cooler
Economizer
Compressor
Motor
Pumpout
Suction Elbow
Miscellaneous Piping
Control Center
Total Rigging Weight
Refrigerant Charge (HFC-134a)
Cooler Water
Condenser Water
Total Operating Weight
6032
6032L
22,000
28,000
31,000
31,000
1,900
1,900
11,000
11,000
6,000
6,000
5,000
5,000
200
200
500
500
750
750
100
100
78,450
84,450
5,050
5,850
4,250*
4,250*
3,100†
4,300†
90,850
98,850