Fan Performance 50Heq006 — Horizontal Discharge Units; High-Static Motor (Belt Drive) - Carrier 50HJQ004-016 Product Data

Single-package rooftop standard and high efficiency heat pump units
Table of Contents

Advertisement

FAN PERFORMANCE 50HEQ006 — HORIZONTAL DISCHARGE UNITS; HIGH-STATIC MOTOR (BELT DRIVE)*
AIRFLOW
AIRFLOW
0.2
(Cfm)
(Cfm)
Rpm
Bhp
1500
724
0.33
1600
757
0.39
1700
790
0.45
1800
823
0.52
1900
857
0.59
2000
892
0.67
2100
927
0.77
2200
962
0.87
2300
997
0.97
2400
1033
1.09
2500
1069
1.22
AIRFLOW
AIRFLOW
1.2
(Cfm)
(Cfm)
Rpm
Bhp
1500
1188
1.09
1600
1208
1.16
1700
1229
1.24
1800
1250
1.33
1900
1273
1.43
2000
1296
1.53
2100
1320
1.64
2200
1345
1.77
2300
1371
1.90
2400
1397
2.04
2500
1424
2.19
LEGEND
Bhp --- Brake Horsepower Input to Fan
Watts --- Input Watts to Motor
* Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive.
NOTES:
Grey box indicates field-supplied drive is required.
Maximum continuous bhp is 2.90.
See General Fan Performance Notes.
1. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage
ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be
affected.
For
additional
performance, refer to Indoor-Fan Motor Performance table
on page 126.
2. Values include losses for filters, unit casing, and wet coils.
See page 127 for accessory/FIOP static pressure
information.
EXTERNAL STATIC PRESSURE (in. wg)
0.4
Watts
Rpm
Bhp
Watts
295
837
0.45
402
343
866
0.51
455
398
894
0.58
514
458
924
0.65
579
525
955
0.73
650
599
986
0.82
729
680
1017
0.92
815
769
1050
1.02
909
865
1082
1.14
1010
970
1115
1.26
1120
1084
1149
1.39
1239
EXTERNAL STATIC PRESSURE (in. wg)
1.4
Watts
Rpm
Bhp
Watts
970
1261
1.29
1143
1033
1279
1.36
1208
1103
1299
1.44
1280
1181
1319
1.53
1360
1266
1341
1.63
1447
1359
1363
1.74
1542
1459
1386
1.85
1646
1568
1409
1.98
1758
1686
1434
2.11
1878
1812
1459
2.26
2008
1948
1484
2.42
2147
GENERAL NOTES FOR FAN PERFORMANCE TABLES
information
on
motor
0.6
Rpm
Bhp
Watts
Rpm
937
0.59
524
1028
962
0.65
580
1050
988
0.72
643
1074
1015
0.80
712
1099
1043
0.89
787
1125
1072
0.98
870
1151
1101
1.08
960
1178
1131
1.19
1059
1206
1161
1.31
1165
1235
1192
1.44
1279
1264
1223
1.58
1403
1293
1.6
Rpm
Bhp
Watts
Rpm
1330
1.49
1327
1395
1347
1.57
1394
1412
1366
1.65
1468
1429
1385
1.74
1549
1448
1405
1.84
1638
1467
1427
1.95
1736
1488
1448
2.07
1842
1508
1471
2.20
1956
1530
1494
2.34
2080
1553
1518
2.49
2213
1576
1543
2.65
2355
1599
3. Use of a field-supplied motor may affect wire sizing.
Contact your Carrier representative for details.
4. Interpolation is permissible. Do not extrapolate.
5. Field- -supplied drive requires changing belt and motor
pulley to meet desired air flow. See application data or
contact your local Carrier reepresentative for details.
160
0.8
1.0
Bhp
Watts
Rpm
Bhp
0.74
660
1111
0.91
0.81
719
1132
0.98
0.88
784
1154
1.06
0.96
857
1177
1.14
1.05
936
1201
1.23
1.15
1022
1226
1.33
1.26
1116
1251
1.44
1.37
1218
1277
1.56
1.50
1329
1304
1.69
1.63
1448
1332
1.83
1.77
1576
1360
1.98
1.8
2.0
Bhp
Watts
Rpm
Bhp
1.71
1523
1457
1.95
1.79
1590
1474
2.02
1.88
1665
1490
2.11
1.97
1748
1508
2.20
2.07
1839
1527
2.31
2.18
1939
1546
2.42
2.30
2047
1566
2.55
2.44
2164
1587
2.68
2.58
2290
1609
2.83
2.73
2425
2.89
2571
Watts
808
870
938
1013
1096
1185
1283
1389
1503
1625
1757
Watts
1729
1797
1873
1957
2050
2151
2262
2380
2509

Hide quick links: