ELECTRICAL DATA — 50HJQ (CONT)
50HJQ004-012 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (CONT)
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
50HJQ
50HJQ
(V-Ph-Hz)
(V-Ph-Hz)
Min
208/230-3-60
187
008
008
1
(7
/
Tons)
2
460-3-60
414
208/230 3 60
208/230-3-60
187
187
009
009
1
1
(8
(8
/
/
Tons)
Tons)
2
2
460-3-60
460 3 60
414
414
208/230-3-60
187
012
012
(10 Tons)
460-3-60
414
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
— Maximum Overcurrent Protection
MOCP
NEC
— National Electrical Code
OFM
— Outdoor Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v.
If power distribution voltage to unit varies from rated heater voltage, heat-
er kW will vary accordingly.
{Heaters are field installed only.
**Fuse or HACR circuit breaker.
{{Electrical disconnect cannot be used if electric heater is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
COMPRESSOR
OFM
(each)
(each)
Max
RLA
LRA
FLA
254
12.4
88.0
1.4
508
6.4
44.0
0.7
254
254
13 9
13.9
105
105
1 4
1.4
508
508
7.9
7 9
55.0
55 0
0.7
0 7
254
19.3
123.0
1.4
508
10.0
62.0
0.7
3
IFM
ELECTRIC HEAT*
FLA
kW†
FLA
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
7.5
18.6/24.8
51.6/ 59.7
107.5/117.6
24.0/32.0
66.6/ 77.0
126.3/139.3
31.8/42.4
88.3/102.0
153.4/170.5
13.9
16.7
16.5
19.8
3.4
27.8
33.4
33.0
39.7
41.7
50.2
46.1/ 46.1
7.8/10.4
21.7/ 25.0
73.2/ 77.3
12.0/16.0
33.3/ 38.5
87.7/ 94.2
7.5
7 5
18.6/24.8
51.6/ 59.7
110.6/120.7
24.0/32.0
66.6/ 77.0
129.3/142.3
31.8/42.4
88.3/102.0
156.5/173.6
13.9
16.7
16.5
19.8
3.4
3 4
27.8
33.4
33.0
39.7
41.7
50.2
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
103.3/109.8
10.6
24.0/32.0
66.6/ 77.0
144.9/157.9
31.8/42.4
88.3/102.0
172.0/189.1
37.6/50.0
104.4/120.3
192.1/181.9
16.5
19.8
27.8
33.4
4.8
33.0
39.7
41.7
50.2
50.0
60.1
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:If the supply voltage phase imbalance is more
than 2%, contact your local electrical utility company
immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
* Single or three phase
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP .
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 50TFQ006---5 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP , then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If "MCA New" is larger than the published
MOCP , raise the MOCP to the next larger size. In all cases, the MOCP for the pow-
er exhaust should be 15 amps per NEC.
125
MINIMUM UNIT
POWER SUPPLY
MCA
MOCP**
FLA
45/ 45
43.0/ 43.0
46/ 46
80/ 80
70.1/ 74.3
71/ 75
90/100
84.6/ 91.1
84/ 90
110/125
105/115
122/134
150/150
147/163
175/175
25
21.4
23
45
42.3
42
50
46.1
46
63.1
70
61
71.0
68
80
84.1
80
90
50/ 50
49/ 49
80/ 80
74/ 78
90/100
87/ 93
125/125
108/118
150/150
126/138
175/175
151/166
24.5
25
26
45.3
50
45
49.2
50
49
66.2
70
64
74.1
80
72
87.2
90
84
70/ 70
61.6/ 61.6
65/ 65
90/100
88.8/ 92.9
90/ 94
110/110
104/110
150/175
142/154
167/183
175/200
185/204
200/200
35
30.9
33
60
55.6
55
80
72.6
71
80.5
90
78
93.6
90
100
91.0
102
100
1371
=
3
=
457
7
457
= 1.53%
APPLICATION
MCA
MCA
MCA
USAGE
(230v)
(460v)
(575v)
1.6
004--- 007*
N/A
0.64
0.68
N/A
004--- 007*
N/A
3.4
008--- 014*
N/A
1.32
N/A
008--- 014*
1.4
N/A
1.7
ALL
N/A
0.68
N/A
ALL
0.7
N/A
DISCONNECT
SIZE
LRA
247/247
269/272
280/285††
298/307††
313/324††
335/349††
123
140
143
157
163
174
281/281
303/306
314/319††
332/341††
347/358††
369/383††
145
162
165
179
185
196
341/341
363/366††
375/380††
408/418††
430/443††
446/462††
172
191
205
211
222††
232††
MOCP
separate
power
source only)
15
15
15
15
15
15