ELECTRICAL DATA — 50HJQ (CONT)
50HJQ004-012 — HIGH-STATIC MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (CONT)
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
50HJQ
50HJQ
(V-Ph-Hz)
(V-Ph-Hz)
Min
208/230-3-60
187
008
1
1
(7
(7
/
/ Tons)
Tons)
2
460-3-60
414
208/230 3 60
208/230-3-60
187
187
009
009
1
(8 /
(8
/
Tons)
Tons)
2
2
460-3-60
460 3 60
414
414
208/230-3-60
187
012
012
(10 Tons)
460-3-60
414
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
— Maximum Overcurrent Protection
MOCP
NEC
— National Electrical Code
OFM
— Outdoor Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v.
If power distribution voltage to unit varies from rated heater voltage, heat-
er kW will vary accordingly.
{Heaters are field installed only.
**Fuse or HACR circuit breaker.
{{Electrical disconnect cannot be used if electric heater is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
COMPRESSOR
OFM
(each)
(each)
Max
RLA
LRA
FLA
254
12.4
88.0
1.4
508
6.4
44.0
0.7
254
254
13 9
13.9
105
105
1 4
1.4
508
508
7.9
7 9
55.0
55 0
0.7
0 7
254
19.3
123.0
1.4
508
10.0
62.0
0.7
3
IFM
ELECTRIC HEAT*
FLA
kW†
FLA
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
10.6
18.6/24.8
51.6/ 59.7
105.8/115.9
24.0/32.0
66.6/ 77.0
124.6/137.6
31.8/42.4
88.3/102.0
151.7/168.8
13.9
16.7
16.5
19.8
4.8
27.8
33.4
33.0
39.7
41.7
50.2
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
10 6
10.6
18.6/24.8
51.6/ 59.7
108.9/119.0
24.0/32.0
66.6/ 77.0
127.6/140.6
31.8/42.4
88.3/102.0
154.8/171.9
13.9
16.7
16.5
19.8
4 8
4.8
27.8
33.4
33.0
39.7
41.7
50.2
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
102.9/109.4
15.0
24.0/32.0
66.6/ 77.0
144.5/157.5
31.8/42.4
88.3/102.0
171.6/188.7
37.5/50.0
104.4/120.3
191.7/181.5
16.5
19.8
27.8
33.4
7.4
33.0
39.7
41.7
50.2
50.0
60.1
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:If the supply voltage phase imbalance is more
than 2%, contact your local electrical utility company
immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
* Single or three phase
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP .
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 50TFQ006---5 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP , then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If "MCA New" is larger than the published
MOCP , raise the MOCP to the next larger size. In all cases, the MOCP for the pow-
er exhaust should be 15 amps per NEC.
127
MINIMUM UNIT
POWER SUPPLY
MCA
MOCP**
FLA
45/ 45
41.3/ 41.3
44/ 44
70/ 80
68.4/ 72.6
69/ 73
90/ 90
82.9/ 89.4
82/ 88
110/125
103/113
121/132
125/150
145/169
175/175
20.6
25
22
41.5
45
41
45.4
50
45
62.4
70
60
70.2
80
68
83.4
90
80
44.4/ 44.4
45/ 45
47/ 47
71.5/ 75.6
80/ 80
72/ 76
86.0/ 92.5
90/100
85/ 91
110/125
106/116
150/150
124/136
175/175
149/164
23.7
25
25
44.6
45
44
48.4
50
48
65.4
70
63
73.3
80
71
86.4
90
83
61.2/ 61.2
70/ 70
65/ 65
88.4/ 92.5
90/100
90/ 94
110/110
103/109
150/175
141/153
175/200
166/182
200/200
185/203
35
31.3
33
60
56.1
56
80
73.1
72
80.9
90
79
94.1
91
100
96.4
102
100
1371
=
3
=
457
7
457
= 1.53%
APPLICATION
MCA
MCA
MCA
USAGE
(230v)
(460v)
(575v)
1.6
004--- 007*
N/A
0.64
0.68
N/A
004--- 007*
N/A
3.4
008--- 014*
N/A
1.32
N/A
008--- 014*
1.4
N/A
1.7
ALL
N/A
0.68
N/A
ALL
0.7
N/A
DISCONNECT
SIZE
LRA
267/267
288/292
300/305††
318/336††
333/344††
355/369††
134
150
153
167
173
184
301/301
322/326
334/339††
352/360††
367/378††
389/403††
156
172
175
189
195
206
360/360
382/385††
393/399††
427/437††
448/462††
464/480††
181
201
215
221
231††
241††
MOCP
separate
power
source only)
15
15
15
15
15
15