Specific Details For Units With A Fan With Available Static Pressure (30Rqsy); Partial Heat Reclaim Using Desuper-Heaters (Option 49); Physical Data, 30Rqs/30Rqsy Units With Partial Heat Reclaim Using Desuperheaters (Option 49) - Carrier 30RQ 039 Series Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pumps
Table of Contents

Advertisement

17 - SpECIfIC DETaIlS fOR UNITS WITH a faN
WITH avaIlaBlE STaTIC pRESSURE (30RQSY)
Selection based on the pressure drop
The cooling and heating capacities are given for an
available pressure of 160 Pa and for a unit without filter.
To calculate the performances at other pressure drops
please use the correction factors below.
Cooling mode
30RQSY 039-050/30RQSY 080-120
Duct pressure
fan speed, r/s
drop
0
12.00
50
13.33
100
14.66
130
15.46
160
16.26
200
17.31
240
18.36
30RQSY 060-078/30RQSY 140-160
Duct pressure
fan speed, r/s
drop
0
15.83
50
16.81
100
17.78
130
18.36
160
18.36
180
18.36
18 – paRTIal HEaT REClaIM USING DESUpER-HEaTERS (OpTION 49)
This option permits the production of free hot water using
heat reclaim by desuperheating the compressor discharge
gases. The option is available for the whole 30RQS/30RQSY
range.

18.1 - physical data, 30RQS/30RQSY units with partial heat reclaim using desuperheaters (option 49)

30RQS/RQSY partial heat reclaim mode
Operating weight 30RQS units with RTpf coils*
Standard unit without hydronic module
Standard unit with hydronic module option
Single high-pressure pump
Dual high-pressure pump
Operating weight 30RQSY units with RTpf coils*
Standard unit without hydronic module
Standard unit with hydronic module option
Single high-pressure pump
Dual high-pressure pump
Refrigerant charge, units with RTpf coils
Circuit A
Circuit B
Condensers
Desuperheaters on circuits a and B
Water volume
Water volume
Max. water-side operating pressure without hydronic
module
Water connections
Connections
Outside diameter
*
Weights shown are a guideline only.
40
power input
Cooling capacity
coefficient
coefficient
0.943
1.019
0.962
1.012
0.980
1.006
0.990
1.003
1.000
1.000
1.012
0.998
1.023
0.996
power input
Cooling capacity
coefficient
coefficient
0.929
1.018
0.944
1.016
0.964
1.014
0.978
1.011
1.000
1.000
1.019
0.991
039
kg
515
kg
544
kg
570
kg
530
kg
560
kg
586
R410A
kg
12,5
kg
-
Grooved copper tubes. aluminium fins
Plate heat exchangers
l
0,549
l
-
kPa
1000
Cylindrical, male gas thread
in
1
mm
42
Heating mode
30RQSY 039-050/30RQSY 080-120
Duct pressure
fan speed, r/s
drop
0
18.36
50
18.36
100
18.36
130
18.36
160
18.36
200
18.36
240
18.36
30RQSY 060-078/30RQSY 140-160
Duct pressure
fan speed, r/s
drop
0
18.36
50
18.36
100
18.36
130
18.36
160
18.36
180
18.36
Note:
Pressure drop, clean filter = 6 Pa
Pressure drop, dirty filter = 12 Pa
A plate heat exchanger is installed in series with the air
condenser coils on the compressor discharge line of each
circuit.
The control configuration for the desuperheater option is
factory assembled.
045
050
060
070
522
548
561
562
552
578
591
591
578
603
617
617
537
568
582
582
567
597
611
612
593
623
637
638
13,5
16,5
17,5
18
-
-
-
-
0,549
0,549
0,732
0,732
-
-
-
-
1000
1000
1000
1000
1
1
1
1
42
42
42
42
power input
coefficient
0.990
0.990
0.990
1.000
1.000
1.000
1.010
power input
coefficient
1.000
1.000
1.000
1.000
1.000
1.001
078
080
090
100
569
762
909
917
599
792
941
949
625
818
986
994
589
776
944
953
619
806
975
985
645
832
1020
1030
16,5
21,5
27,5
28,5
-
-
-
-
0,732
0,732
0,976
0,976
-
-
-
-
1000
1000
1000
1000
1
1
1
1
42
42
42
42
Heating capacity
coefficient
1.016
1.012
1.009
1.005
1.000
0.994
0.981
Heating capacity
coefficient
1.026
1.020
1.011
1.007
1.000
0.993
120
140
160
973
1088
1106
1009
1127
1145
1057
1164
1155
1008
1118
1135
1044
1157
1174
1092
1194
1211
33
19
18,5
-
19
18,5
0,976
0,732
0,732
-
0,732
0,732
1000
1000
1000
1
1
1
42
42
42