Select And Install Ductwork; Converting Horizontal Discharge Units To Downflow (Vertical) Discharge - Carrier 50JZ024 Installation, Start-Up And Service Instructions Manual

Single-package heat pump units with puron (r-410a) refrigerant
Table of Contents

Advertisement

A
B
Fig. 5—Unit Leveling Tolerances
OPTIONAL
RETURN
AIR
OPENING
2"
INDOOR COIL
Fig. 6—Slab Mounting Detail
HANDHOLD
HOOK
FEED
Fig. 7—Threading Belt
and the wire tie on the right to be cut is located approximately
6 in. down the tube sheet.
Step 5—Select and Install Ductwork
The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
non-residence type air conditioning and ventilating systems, NFPA
90A or residence-type, NFPA 90B and/or local codes and ordi-
nances.
Select and size ductwork, supply-air registers, and return air grilles
according to ASHRAE (American Society of Heating, Refrigera-
tion, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply- and return-air openings on
the side of the unit.
When designing and installing ductwork, consider the following:
For vertical supply and return units, tools or parts could drop
into ductwork and cause serious injury or death. Install a 90
degree turn in the return ductwork between the unit and the
conditioned space. If a 90 degree elbow cannot be installed,
then a grille of sufficient strength and density should be
installed to prevent objects from falling into the conditioned
space. Units with electric heaters require 90 degree elbow in
supply duct.
1. All units should have field-supplied filters or accessory filter
rack installed in the return-air side of the unit. Recommended
sizes for filters are shown in Table 1.
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
B-C
A-C
1/4
1/4
1/4
C99065
OPTIONAL
SUPPLY
AIR
OPENING
OUTDOOR COIL
C99096
C99067
"A"
"B"
PLACE RIGGING BRACKET ASSEMBLY IN 4
HAND HOLES AND INSTALL TIE DOWN STRAP
AROUND PERIMETER OF UNIT AND THROUGH
SPACE IN BRACKET ASSEMBLY
SEE DETAIL A
UNIT 50JZ
MAXIMUM WEIGHT
Size
lb.
024
321
030
342
036
350
042
372
048
377
060
450
Fig. 8—Suggested Rigging
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between duct-work and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24-in.
from electric heater element.
1. Size ductwork for cooling air quantity (cfm). The minimum
air quantity for proper electric heater operation is listed in
Table 2. Heater limit switches may trip at air quantities below
those recommended.
2. Seal, insulate and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and Air
Conditioning Contractors National Association (SMACNA)
and Air Conditioning Contractors Association (ACCA) mini-
mum installation standards for residential heating and air
conditioning systems.
3. Secure all ducts to building structure. Flash,weatherproof, and
vibration-isolate duct openings in wall or roof according to
good construction practices.
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE UNITS
Before performing service or maintenance operations on
system, turn off main power to unit. Turn off accessory heater
power switch if applicable. Electrical shock could cause
serious injury or death.
1. Open all electrical disconnects before starting any service
work.
6
914-137"
(36"-54")
DETAIL A
SCALE 0.250
TIGHTEN STRAPPING SECURELY
WITH TENSION BUCKLE
INSTALL SAFETY STRAPS TO
RIGGING CLEVIS AT 4 RIGGING BRACKETS
A
B
kg.
in.
mm.
in.
145.6
19.0
482.6
18.25
155.2
20.0
508
19.25
158.8
20.0
508
19.0
168.8
21.0
533.4
20.5
171.0
20.0
508
21.25
204.2
21.0
533.4
20.0
C99075
mm.
463.6
489
482.6
520.7
539.8
508.0