Electric Heating Capacities — 50Tfq008-012 - Carrier 50HJQ004-016 Product Data

Single-package rooftop standard and high efficiency heat pump units
Table of Contents

Advertisement

PERFORMANCE DATA—50TFQ (CONT)
UNIT
UNIT VOLTAGE
50TFQ
(60 Hz)
208/230/240
(3 phase)
008, 009
460/480
(3 phase)
575
(3 phase)
208/230/240
(3 phase)
012
460/480
(3 phase)
575
(3 phase)
*Two heater packages required to provide kW indicated.
†Use CRSINGLE004A00 for units with convenience outlet.
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
2
kW new = 16 kW (215/240)
kW new = 12.8 kW (rating at 215 v)
ELECTRIC HEATING CAPACITIES — 50TFQ008-012
ACCESSORY
kW
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4*
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
17.0
34.0
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/39.0/42.4*
37.6/46.2/50.0*
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7*
45.9/50.0*
17.0
34.0
51.0*
ELECTRIC HEATER
PART NUMBER
CRHEATER---A00
017
010
011
012
012 and 017
016
013
014
015
014 and 016
018
019
017
010
012
012 and 017
010 and 012
013
014
015
014 and 016
013 and 015
018
019
018 and 019
2
55
SINGLE POINT BOX
PACKAGE NO.
CRSINGLE---A00
007
007
009
009
013
006
006
008
008
010
006
006†
012
012
015
017
017
011
014
014
016
016
011
014
016

Hide quick links: