z. Return Air CO
Sensor (EconoMi$er IV):
2
Sensor shall have the ability to provide demand
ventilation control through the EconoMi$er IV. The IAQ
sensor shall be duct mounted. The set point shall have
adjustment capability.
aa. Ultra-Violet Germicidal Lamps:
Ultra-violet germicidal lamps are designed to eliminate
odor-causing mold and fungus that may develop in the
wet area of the indoor section of the unit. The high output,
low temperature germicidal lamps are field installed in
the indoor section of the unit, aimed at the indoor coil and
condensate pan. The short wave-length ultra-violet light
inhibits and kills mold, fungus and microbial growth. The
lamps have an output rating at 45 F in 400 fpm airflow
2
of 120 microwatts/cm
at 1 meter.
ab. Hinged Panel Option:
Hinged panel option provide hinged access panels for the
filter, compressor, evaporator fan, and control box areas.
Filter hinged panels permit tool-less entry for changing
filters. Each hinged panel is permanently attached to the
rooftop unit.
ac. Emergency Heat Control Package:
When mechanical heating is locked out, auxiliary heat
shall be activated when necessary.
138