Carrier 50HJQ004-016 Product Data page 113

Single-package rooftop standard and high efficiency heat pump units
Table of Contents

Advertisement

1
50HJQ009 (8
/
TONS) STANDARD MOTOR (BELT DRIVE)*
2
Airflow
Airflow
0.2
(Cfm)
(Cfm)
Rpm
Bhp
2500
462
0.37
2600
474
0.41
2700
486
0.45
2800
498
0.49
2900
510
0.53
3000
523
0.58
3100
536
0.63
3200
549
0.68
3300
562
0.74
3400
575
0.80
3500
588
0.86
3600
601
0.93
3700
614
1.00
3800
628
1.07
3900
641
1.15
4000
655
1.23
4100
668
1.31
4200
682
1.40
4300
696
1.49
1
50HJQ009 (8
/
TONS) STANDARD MOTOR (BELT DRIVE)* (cont)
2
Airflow
Airflow
1.2
(Cfm)
(Cfm)
Rpm
Bhp
2500
804
1.09
2600
809
1.14
2700
813
1.20
2800
819
1.26
2900
824
1.32
3000
830
1.39
3100
837
1.46
3200
843
1.53
3300
850
1.61
3400
858
1.69
3500
865
1.77
3600
873
1.86
3700
881
1.95
3800
889
2.04
3900
898
2.14
4000
907
2.24
4100
916
2.35
4200
925
2.45
4300
934
2.57
LEGEND
Bhp --- Brake Horsepower Input to Fan
Watts --- Input Watts to Motor
* Motor drive range: 840 to 1085 rpm. All other rpms require a field-
supplied drive.
See General Fan Performance notes.
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (CONT)
External Static Pressure (in. wg)
0.4
Watts
Rpm
Bhp
Watts
348
541
0.50
467
381
551
0.54
505
417
561
0.58
545
456
571
0.63
587
497
581
0.68
632
541
592
0.73
680
587
603
0.78
730
637
614
0.84
783
689
626
0.90
839
744
637
0.96
898
802
649
1.03
961
864
661
1.10
1026
929
673
1.17
1095
997
685
1.25
1167
1069
697
1.33
1243
1144
709
1.42
1322
1223
722
1.51
1405
1305
734
1.60
1492
1392
747
1.70
1582
External Static Pressure (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1013
861
1.25
1164
1065
864
1.31
1219
1119
869
1.37
1277
1176
873
1.43
1337
1235
878
1.50
1400
1298
883
1.57
1466
1363
889
1.65
1534
1431
894
1.72
1606
1502
901
1.80
1680
1576
907
1.88
1758
1653
914
1.97
1838
1733
921
2.06
1922
1816
928
2.16
2010
1904
936
2.25
2100
1995
944
2.35
2195
2089
952
2.46
2293
2187
960
2.57
2395
2289
969
2.68
2500
2395
978
2.80
2610
0.6
Rpm
Bhp
Watts
Rpm
614
0.64
594
681
622
0.68
635
688
630
0.73
679
695
639
0.78
725
702
648
0.83
774
710
657
0.88
825
718
666
0.94
879
726
676
1.00
936
735
686
1.07
996
743
696
1.14
1059
752
707
1.21
1125
762
717
1.28
1194
771
728
1.36
1267
781
739
1.44
1343
791
750
1.53
1423
801
761
1.61
1506
812
773
1.71
1593
822
784
1.80
1683
833
796
1.91
1777
844
1.6
Rpm
Bhp
Watts
Rpm
915
1.41
1319
967
918
1.48
1378
969
921
1.54
1439
972
925
1.61
1503
975
929
1.68
1569
978
934
1.76
1638
982
938
1.83
1710
986
944
1.91
1785
991
949
2.00
1863
996
955
2.09
1944
1001
961
2.18
2029
1007
967
2.27
2116
1012
974
2.37
2207
1019
981
2.47
2302
1025
988
2.57
2399
1032
996
2.68
2501
1004
2.80
2607
NOTES:
.
1
Shaded cells indicate field-supplied drive is required.
.
2
Maximum continuous bhp is 2.90.
113
0.8
1.0
Bhp
Watts
Rpm
Bhp
0.78
728
744
0.93
0.83
773
750
0.98
0.88
820
756
1.04
0.93
870
762
1.09
0.99
922
768
1.15
1.05
977
775
1.22
1.11
1035
783
1.28
1.17
1096
790
1.35
1.24
1159
798
1.42
1.31
1226
806
1.50
1.39
1296
815
1.58
1.47
1369
823
1.66
1.55
1445
832
1.75
1.64
1525
841
1.84
1.72
1608
850
1.93
1.82
1695
860
2.03
1.92
1786
870
2.13
2.02
1880
880
2.23
2.12
1979
890
2.34
1.8
2.0
Bhp
Watts
Rpm
Bhp
1.59
1479
1017
1.76
1.65
1541
1018
1.83
1.72
1606
1021
1.90
1.79
1673
1023
1.98
1.87
1742
1026
2.06
1.95
1815
1029
2.14
2.03
1891
1033
2.23
2.11
1969
1037
2.31
2.20
2051
1041
2.40
2.29
2135
1046
2.50
2.38
2223
1051
2.60
2.48
2314
1056
2.70
2.58
2409
1062
2.80
2.69
2507
2.80
2608
Watts
868
916
967
1020
1076
1135
1196
1260
1328
1398
1472
1548
1629
1712
1799
1890
1984
2082
2184
Watts
1642
1708
1776
1847
1920
1996
2075
2157
2242
2331
2422
2516
2615

Hide quick links: