*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW
new = Heater kW rated x (unit power distribution voltage/rated heater voltage)
3. The minimum airflow for a 50HJQ005 with two (2) CRHEATER004A00 (21 kW) modules at 230 volts, is 350 cfm/ton (1400cfm).
4. Single point boxes contain a junction box, wiring and sub---fusing assembly as necessary to meet National Electric Cod and UL requirements. Single
point boxes CRSINGLE001A00, 006A00 and 011A00 are junction boxes only.
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
2
kW
new = 16 kW (215/240)
kW
new = 12.8 kW (rating at 215 v). Single point boxes CRSINGLE001A00, 006A00 and 011A00 do not include fuses and fuses are not required per the National Electric Code in these
single point boxes since sub--- fusing is not required below 60 amps.