Carrier 50HJQ004-016 Product Data page 123

Single-package rooftop standard and high efficiency heat pump units
Table of Contents

Advertisement

ELECTRICAL DATA — 50HJQ (CONT)
50HJQ004-012 STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENT OUTLET (CONT)
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
50HJQ
50HJQ
(V-Ph-Hz)
(V-Ph-Hz)
Min
208/230-3-60
187
008
008
1
(7
/
Tons)
2
460-3-60
414
208/230-3-60
208/230 3 60
187
187
009
009
1
1
(8
(8
/
/
Tons)
Tons)
2
2
460-3-60
460 3 60
414
414
208/230-3-60
187
012
012
(10 Tons)
460-3-60
414
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP
— Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor Fan Motor
RLA
— Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v.
If power distribution voltage to unit varies from rated heater voltage, heat-
er kW will vary accordingly.
{Heaters are field installed only.
**Fuse or HACR circuit breaker.
{{Electrical disconnect cannot be used if electric heater is installed.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-
tective device for the unit shall be fuse or HACR breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of
voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
COMPRESSOR
OFM
(each)
(each)
Max
RLA
LRA
FLA
254
12.4
88.0
1.4
508
6.4
44.0
0.7
254
254
13 9
13.9
105
105
1 4
1.4
508
508
7.9
7 9
55 0
55.0
0 7
0.7
254
19.3
123.0
1.4
508
10.0
62.0
0.7
IFM
ELECTRIC HEAT*
FLA
kW†
FLA
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
7.5
18.6/24.8
51.6/ 59.7
102.7/112.8
24.0/32.0
66.6/ 77.0
121.5/134.5
31.8/42.4
88.3/102.0
148.6/165.7
13.9
16.7
16.5
19.8
3.4
27.8
33.4
33.0
39.7
41.7
50.2
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
7.5
7 5
18.6/24.8
51.6/ 59.7
105.8/115.9
24.0/32.0
66.6/ 77.0
124.5/137.5
31.8/42.4
88.3/102.0
151.7/168.8
13.9
16.7
16.5
19.8
3.4
3 4
27.8
33.4
33.0
39.7
41.7
50.2
7.8/10.4
21.7/ 25.0
12.0/16.0
33.3/ 38.5
10.6
24.0/32.0
66.6/ 77.0
140.1/153.1
31.8/42.4
88.3/102.0
167.2/184.3
37.6/50.0
104.4/120.3
187.3/177.1
16.5
19.8
27.8
33.4
4.8
33.0
39.7
41.7
50.2
50.0
60.1
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:If the supply voltage phase imbalance is more
than 2%, contact your local electrical utility company
immediately.
POWER EXHAUST ELECTRICAL DATA
POWER EXHAUST
PART NO.
CRPWREXH030A01
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
* Single or three phase
N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP .
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 50TFQ006---5 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP , then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If "MCA New" is larger than the published
MOCP , raise the MOCP to the next larger size. In all cases, the MOCP for the pow-
er exhaust should be 15 amps per NEC.
123
MINIMUM UNIT
POWER SUPPLY
MCA
MOCP**
FLA
40/ 40
38.2/ 38.2
40/ 40
70/ 70
65.3/ 69.5
65/ 69
80/ 90
79.8/ 86.3
79/ 85
110/125
100/109
117/129
125/150
142/158
150/175
20
19.2
20
45
40.1
39
45
44.0
43
61.0
70
59
68.8
66
70
82.0
78
90
41.3/ 41.3
45/ 45
43/43
68.4/ 72.5
70/ 80
68/72
82.9/ 89.4
90/ 90
82/88
110/125
103/112
125/150
120/132
175/175
145/161
22.3
25
23
43.2
45
43
47.0
50
46
64.0
70
62
71.9
80
69
85.0
90
81
60/ 60
56.8/ 56.8
60/ 60
90/ 90
84.0/ 88.1
85/ 89
100/110
98.5/105.0
98/104
150/175
136/148
161/177
175/200
180/198
200/200
30
28.7
30
60
53.5
53
80
70.5
69
78.3
80
76
91.5
88
100
88.8
99
100
452 + 464 + 455
3
1371
=
3
=
457
7
457
= 1.53%
APPLICATION
MCA
MCA
MCA
USAGE
(230v)
(460v)
(575v)
1.6
004--- 007*
N/A
0.64
0.68
N/A
004--- 007*
N/A
3.4
008--- 014*
N/A
1.32
N/A
008--- 014*
1.4
N/A
1.7
ALL
N/A
0.68
N/A
ALL
0.7
N/A
DISCONNECT
SIZE
LRA
242/242
264/267
275/281††
294/302††
309/319††
330/344††
121
138
141
155
161
171
276/276
298/301
309/315††
328/336††
343/353††
364/378††
143
160
163
177
183
193
337/337
358/362††
370/375††
403/414††
425/439††
441/457††
170
189
203
209
220††
230††
MOCP
separate
power
source only)
15
15
15
15
15
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents