Insert Clearances; Mantel Requirements; Hearth Requirements - Travis Industries DVL Insert Owner's Manual

Direct vent fireplace insert
Hide thumbs Also See for DVL Insert:
Table of Contents

Advertisement

Installation
8

Insert Clearances

No combustibles may be within, or swing within, 36" of the front of the insert (drapes, doors)
Max. 8"
Side Facing
Mantel Clearances
The mantel must be a minimum 10" above the face and a maximum 8" deep.
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.

Hearth Requirements

The heater must be installed on a non-combustible hearth extending a minimum 12" from the fireplace
opening (local codes may require a larger hearth). The hearth must also extend to both sides of the
face (see the table above for the exact width of the face).
Travis Industries
Min. 8-1/2"
Min. 6"
12" Min. (from fireplace opening)
(for qualified installers only)
Min. 10"
See Table Below
Face Sizing
Discovery, Rosario
Heritage Bay
Salish Bay
Cambridge
FPX Arched or Rect.
4 0 1 1 0 2 5
Side
Wall
Min. 6"
The non-combustible hearth
must be as wide as the face
and extend to both sides.
Width
Height
35-3/4"
26"
35-3/8"
25-5/8"
33-1/2"
26-3/8"
36-1/4"
25-7/8"
34-3/4"
26-1/2"
9 3 5 0 8 1 0 4