Table R. Power Cable Conduit Requirements Powerware BPIV (20 kVA -- 30 kVA)
Powerware
System
BPIV ---30/30
BPIV ---30/30
BPIV ---30/30
BPIV ---30/30
A ---14
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
208
AC Input to Bypass
(A, B, C, Neut, Gnd)
AC
AC
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480
AC
C
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
600
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
Number of
Wires in
Conduit
4
5
5
4
5
5
4
5
N/A
3
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201406---1
REVISION: C
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
Minimum
Conduit
Number of
Trade Size
Conduits
(inches)
1-1/2
1
1-1/2
1
1-1/2
1
1
1
1
1
1
1
3/4
1
3/4
1
N/A
N/A
1-1/4
1
SHEET:
13 of 14
DATE:
013004
164201406 Rev. C 013004