Per NEC article 300-20(a), all three phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
11.
Conduit is sized to accommodate one neutral conductor the same size as the phase
conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized
neutral conductor are to be installed, check the size of the conduit needed to
accommodate the extra wire or size and use that conduit size in place of the conduit size
listed in tables P through R. All Powerware BPIV products can accommodate a double
size neutral.
12.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW,
THHW, THW-2.
Table P. Power Cable Conduit Requirements Powerware BPIV (10 kVA -- 15 kVA)
Powerware
System
BP-IV ---15/10
BP-IV ---15/10
BP-IV ---15/10
BP-IV ---15/15
BP-IV ---15/15
BP-IV ---15/15
A ---12
Voltage
Terminal
AC Input to UPS
(A, B, C, Gnd)
208
AC Input to Bypass
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480/600
AC
C
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
208 AC
(A, B, C, Neut, Gnd)
Output
(A, B, C, Neut, Gnd)
288
External Battery DC Source
DC
(Positive, Negative, Gnd)
AC Input to UPS
(A, B, C, Gnd)
AC Input to Bypass
480/600
(A, B, C, Neut, Gnd)
AC
C
Output
(A, B, C, Neut, Gnd)
Number of
Wires in
Conduit
4
5
5
4
5
5
3
4
5
5
3
4
5
5
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201406---1
REVISION: C
Powerware BPIV (10 kVA- -30 kVA) Installation and Operation
Minimum
Conduit
Number of
Trade Size
Conduits
(inches)
3/4
1
3/4
1
3/4
1
1/2
1
1/2
1
1/2
1
1/2
1
3/4
1
1
1
1
1
3/4
1
1/2
1
3/4
1
3/4
1
SHEET:
11 of 14
DATE:
013004
164201406 Rev. C 013004