4-5 Installation Environment

4-5-1 Handling Safety

1. The Protect 3.M 2.0 Series UPS is equipped with casters so that you can roll the
UPS in a short distance to the desired location. During unpacking process, be
sure to make full use of manpower and a suitable machine (such as stacker) with
sufficient capacity to carefully move the UPS.
Please pay extremely close attention while unbolting the UPS from the shipping
pallet. Prevent any accident resulting from unexpected move.
2. Casters are only suitable for moving on even surface. Avoid moving the UPS on
bumpy route, because this may cause damage of UPS or tip-over accident.
3. Push the UPS from either front or rear side otherwise could cause tip-over accident.
4. When the UPS needs a long-distance movement, make use of a suitable machine
but not casters of the UPS.

4-5-2 UPS Positioning

1. Position the UPS or external battery pack by suitable machine.
2. Refer to Table 4-1 to 4-4. Ensure that the UPS is positioned at a suitable floor
which can sustain for the weight.
3. After positioning the UPS, ensure to push C (Stop) to "ON" until strictly fastened
and adjust leveler to the floor.
A
4-5
A: Leveler
B
B: Caster
C: Stop
C