Preparations; Wiring (Single Unit) - AEG 80 / 120 kVA Operating Instructions Manual

Uninterruptible power supply 80 / 120 kva model
Table of Contents

Advertisement

4-6 Wiring

4-6-1 Preparations

1. The UPS should only be installed by a qualified electrically employed person
2. De-energize all input (AC or DC) or output power of the UPS before installing
cables
or making any electrical connection.
3. Ensure that all cables are correctly marked according to the purpose, as well as
the
polarity, phase and diameter.
4. If the input/output power of the UPS is WYE-WYE (Y connection), "Neutral"
and "Ground" should not be connected.
If the input power has V
before UPS and input power source. Then, connect "Neutral" and "Ground" of
the UPS together.
5. Make use of suitable conduits and gland to protect I/O wiring according to local
regulations. Refer to Table 4-3.
6. If after the installation many cables are ducted very close together it is
recommended to use cables with isolations made for higher temperature ranges.
 Table 4-3 Input/Output Electrical Data
UPS
module
Input
Output
quantity
(V)
1
230/400
230/400
(20kVA)
2
230/400
230/400
(40kVA)
3
230/400
230/400
(60kVA)
4
230/400
230/400
(80kVA)
5
230/400
230/400
(100kVA)
6
230/400
230/400
(120kVA)
* Recommended cross section following DIN EN 60269-1 (single wire cables in
free air). Please consider possible deviation due to installed region.
7. Confirm the power phase of L1, L2 and L3.
8. Confirm the polarity of battery cable.
9. Connect the ground of external battery cabinet to UPS's ground.
10. Connect the UPS's ground to the protective earth.
>0, the solution is to install an isolation transformer
NG
Input
Input
Fuse
Cable
(V)
NH, gL
(mm²)
(A)
35
6
63
16
100
25
125
35
160
50
200
70
Reserve
Reserve
Output
Fuse
Cable
Fuse
NH, gL
NH, gL
(mm²)
(A)
50
6
75
16
125
25
150
35
200
50
250
70
4-8
Output
Battery
Cable
Fuse
NH, gL
(mm²)
(A)
(A)
50
6
50
75
16
80
125
25
125
150
35
160
200
50
200
250
70
250
Battery
Cable
(mm²)
6
16
35
50
70
95