The Protect 3.M 2.0 Series UPS provides 6 dry contact outputs. These contacts can
be set to normally open or normally close. The default message is shown in the table
below.
Contact Message
Pin1-2
Load on inverter
Pin3-4
Load on auto bypass
Pin5-6
Mains1 input fails when
loading on inverter
Pin7-8
Battery low
Bypass input abnormal
Pin9-10
Pin11-12 Battery test failure
There are other 13 choices as shown below.
Contact Message
7.
Internal communication
failure
8.
External parallel
communication failure
9.
Output overload
warning/shutdown
10.
Power module fault
shutdown
11.
Power module warning
12.
EPO activated
13.
Load on manual bypass
Battery cabinet over
14.
temperature
warning/shutdown
15.
Output voltage abnormal
16.
Battery need replace
17.
Bypass over temperature
warning/shutdown
18.
Battery ground fault
19.
Bypass static switch fault
20.
Summary Alarm
Description
The UPS is working normally.
The UPS is in bypass mode.
The Utility is blackout or abnormal. The UPS is in backup
mode.
The UPS is in backup mode, and the battery voltage is closed
to the terminative limit. (The battery voltage is lower than
220V.)
The bypass is abnormal (frequency, phase), and the output
frequency will follow the rating.
Performs the battery test. The battery voltage is lower than the
default value.
Description
The communication of module is abnormal.
During installation of the parallel redundancy, the parallel
communication is abnormal.
The loading is over rated output of the UPS.
The module fails and the UPS is shut down.
The module has errors, but the UPS can still function
normally.
Urgently power off the UPS.
The UPS transfers to manual bypass mode.
The temperature is too high.
The output voltage is too high or too low.
Overdue for battery replacement (Compared with system
setup.)
Bypass "static transfer switch" is over temperature.
Grounding error
The bypass "static transfer switch" is abnormal.