Pipe Selection Chart - Quadra-Fire Edge60 Owner's Manual

Zero clearance pellet fireplace nutural/curved/tuscan/studio
Table of Contents

Advertisement

R
R R
G. Pipe Selection Chart
The chart will help you in determining proper venting size
according to the equivalent feet of pipe calculated previously
and the altitude above sea level of this installation.
Figure 41.1.
a. Locate the calculated equivalent feet of pipe on the verti-
cal left side of the chart.
b. Move to the right horizontally on the chart until you reach
your altitude above sea level.
c. If you fall below the diagonal line,  or 4 inch (76 to
10mm) pipe may be used.
d. If it is anywhere above the diagonal line, a 4 inch (10mm)
diameter pipe is required.
NOTICE:
• A 90° elbow is 5 times as restrictive to the flow of exhaust
gases under positive pressure as 1 foot (05mm) of hori-
zontal pipe.
• A foot of horizontal pipe is twice as restrictive as a foot of
vertical pipe.
30
Example 1
20
Equivalent Pipe
Length In Feet
Example 
10
3 in. or 4 in. (76mm or 102mm) Diameter Pipe
0
1
ALTITUDE IN THOUSANDS OF FEET
Figure 41.1
Example 1: If the equivalent length of pipe is  feet (.58m) with alti-
tude of 8,000 feet (0m) you must use 4 inch (10mm) diameter type
"L" or "PL" vent.
Example 2: If the equivalent length of pipe is 1 feet (.0m) with altitude
of 6,000 feet (15m) you may use  or 4 inch (76 to 10mm) diameter
type "L" or "PL" vent/.
April 9, 2009
4 in. (102mm) Diameter Pipe Only
2
3
4
5
6
7
WARNING! RISK OF FIRE!
Do NOT pack insulation or other combustibles between
firestops.
• ALWAYS maintain specified clearances around venting
and firestop systems.
• Install firestops as specified.
Failure to keep insulation or other material away from vent
pipe may cause fire.
8
9
10
7051-158
EDGE 60 Pellet Fireplace
Page 41