4.7 Electrical connections

Only qualified professionnals may carry out electrical
connections, always with the power off.
Do not modify the connections inside the control panel.
Make the electrical connections of the appliance according to:
- the instructions of the prevailing standards,
- the instructions on the circuit diagrams provided with the
appliance,
- the recommendations in the instructions.
Standards to be respected
Other countries: The electrical connections shall comply with
standards in force.

4.8 Skeleton Diagrams

Control panel instructions
14
Rules to be respected
- Power the appliance via a circuit which includes a remote
omnipolar switch with a gap of more than 3 mm.
- Connect all of the cables to the terminal blocks in the control panel.
Keep to the polarity shown on the terminals: phase (L),
neutral (N) and earth
The available output per outlet is 450 W (2 A, with cos
0.7) and the inrush current must be lower than 16 A.
If the charge exceeds one of these values, relay the
command using a contactor (fitted outside the control
panel).
Separate the sensor cables from the 230 V cables.
Outside the boiler : Use 2 pipes or cable guides at least
10 cm apart.
For the 230 V electrical connections, use 3-wire cables with a cross-
section of 0.75 mm². For other electrical connections, use the 3 wire
cable with a diameter of 0.75 mm².
Make the electrical connections:
Control panel instructions.
Options brochure.