Main Dimensions; Assembling The Appliance - REMEHA GAS 460 S Installation And Service Manual

Gas-fired boilers
Hide thumbs Also See for GAS 460 S:
Table of Contents

Advertisement

4.3.2
Ventilation
The location of air inlets in relation to the high ventilation openings
shall ensure that the air is renewed in the entire volume of the boiler
room.
Please refer to the prevailing regulations in your country.
France:
Direct air inlet:
Boiler with nominal output greater than 70 kW in accordance
with DTU 65.4 (NF P 52-221)
Upper and lower air vents compulsory
- Upper air vents
Cross section equal to half the total cross section of the flue gas
pipes with a minimum of 2.5 dm²
4.3.3

Main dimensions

Heating outlet R 2
Heating return R 2
Boiler Gas 460 S
A (mm)
B (mm)
Ø C (mm)
D (mm)
E (mm)
Ø F (mm) (20/25 mbar)
Ø F (mm) (300 mbar)
G
H
J
4.3.4

Assembling the appliance

See assembly instructions
04/01/11 - 300005247-001-E
/8
/10
1362
1362
970
1146
250
300
632
808
165
165
Rp1
Rp1
447
535
445
445
1094
1094
GAS 460 S
- Lower air vents
Direct air inlet:
0 86P
,
2
(
)
------------- -
S dm
20
P = Installed output in kW
Ensure a supply of air through the front of the burner but
avoid serious draughts.
Bottom aeration, even correctly dimensioned but positioned to the
rear of the boiler close to the draught diverter, may turn out to be
totally ineffective.
Incoming air is directly drawn in by the draught cut off without
reaching the burner.
An indirect air inlet through descending conduits presenting serious
airotic losses of load or input of meteorological conditions influencing
their draw should be avoided.
Draining Rp 3/4
/12
/14
1362
1412
1322
1498
300
350
984
1160
165
190
Rp1
Rp1 1/4
Rp 1 1/4
Rp 3/4
623
704
445
454
1094
1194
/16
/18
1412
1412
1674
1850
350
350
1336
1512
190
190
Rp 1 1/4
Rp 1 1/2
792
880
454
454
1194
1194
/20
1462
2026
400
1688
220
963
507
1194
11