Setting the start-up progressivity (or initial flow)
In the factory, the progressivity is set to minimum (low start-up
pressure).
5.3.4
Setting the gas pressure switch
The minimum gas pressure switch on the safety valve is set in the
factory to a value of 12.5 mbar, which corresponds to the setting for
natural gas.
If there is a drop in the gas supply pressure, the minimum pressure
switch shuts down the boiler.
5.3.5
Attaching the label
Affix the label which indicates for which type of gas the boiler is fitted
and set.
04/01/11 - 300005247-001-E
Depending on the installation conditions, adjust the progressivity
setting in order to guarantee optimum boiler start-up.
- Unscrew the protection cap G. Use like a spanner to turn the
setting rod H until you obtain the desired initial flow.
- Put the cap back in place.
GAS 460 S
19