Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
2.
3.
4.
5.
6.
7.
EATON Powerware
Press any button on the front panel display to activate the menu
options.
Using the
button, scroll to the Settings menu.
Press the
button twice to select the User Settings menu.
Using the button, scroll to the Number of Battery Strings option
and press the
button.
Use the
or buttons to select the number of strings according to
your UPS configuration:
All 2-High UPS and EBM Cabinets*
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
All 3-High UPS and EBM Cabinets*
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
* UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
Press the
button to save the setting.
ESC
Press the
button until the Eaton Powerware logo appears.
®
9355 UPS (10/15 kVA) User's Guide
Number of Strings
6
10
14
18
Number of Strings
10
16
22
S
164201594 Rev C www.powerware.com
OPERATION
77