CN63300 Water Processing Application

A city water company needs to maintain a steady flow of water for their
customer needs. They have an existing 0 to 10 VDC flow transmitter to
measure the water flow. They need to control the water flow, have a high and
low alarm, and keep a recorded chart of the flow for later reference. The Main
Linear DC output of the CN63300 is used to control the position of water
value to maintain the desired flow setpoint value. The CN63300 relay outputs
are programmed to give a high flow alarm and a low flow alarm. With the
Second Linear DC output model, the flow measurement to the CN63300 can
be retransmitted to a chart recorder.
ALARM
POWER
+
-
HIGH
LOW
ALARM
ALARM
CONTROL
VALVE
Figure 38, Water Processing Application
CHART
RECORDER
UNIT POWER
FLOW
SENSOR
WATER FLOW
Process Requirements
Unprotected Parameters
ProP
XX
Calculated by Auto-Tune
Intt
XX
Calculated by Auto-Tune
dErt
XX
Calculated by Auto-Tune
AL-1
90.0
High alarm
AL-2
20.0
Low alarm
1-IN Configure Input Parameters
tYPE
VOLt
Voltage Input
dCPt
0.0 *
Resolution
FLtr
XX
Calculated by Auto-Tune
dSP1
0.0
Input low value
INP1
0.00
Low display value
dSP2
10.0
Input high value
INP2
150.00
High display value
SPLO
40.0
Setpoint low limit
SPHI
80.0
Setpoint high limit
SPrP
0.0 *
No ramping
INPt
PLOC *
User input program lock
2-OP Configure Output Parameters
CYCt
0
Disable O1 output
The remaining parameters in this module are set to factory settings.
4-AL Configure Alarm Parameters
Act1
A-HI
Set 01/A1 for control output
rSt1
LAtC
Manual reset
Stb1
yes
Disable alarm during power-up
AL-1
90.0
Set 90.0 gal/min high alarm value
Act2
A-LO
Set alarm #2 for deviation band from setpoint
rSt2
LAtC
Manual reset
Stb2
yes
Disable alarm during power-up
AL-2
20.0
Set 20.0 gal/min low alarm value
AHYS
5.0
Alarm activation hysteresis
8-A2 Configure Second Analog Parameter
A2tP
4-20
4-20 mA retransmitted
A2LO
0.0
Display low value
A2HI
150.0
Display high value
* Factory Settings
-66-