Configure Module 7 - Remote Setpoint Parameters (7-rS or
7-n2)
Controller returns to configuration access point (CnFP NO) if remote
setpoint option is not installed.
Display
Parameter
dSP1
Remote setpoint
display scaling point
#1
INP1
Remote setpoint
input scaling point
#1.
dSP2
Remote setpoint
display scaling point
#2
INP2
Remote setpoint
input scaling point
#2
FLtr
Remote setpoint
filter time constant
bAnd
Remote setpoint
filter band
trnF
Remote/Local
setpoint transfer
options
Range and Units
Description/
(Factory Setting)
Comments
-999 to 9999
Remote setpoint
(0) CN63100
display low value.
(0.0) CN63300
0.00 to 20.00 mA
Key in input low
(4.00)
value or Press D to
select Signal Input
method.
-999 to 9999
Remote setpoint
(1000) CN63100
display high value.
(100.0) CN63300
0.00 to 20.00 mA
Key in input low
(20.00)
value or Press D to
select Signal Input
method.
0 to 25 seconds
0 = off
(2)
0 to 250
0 = filter always
(5)
engaged.
nor - normal
Auto = Bumpless,
Auto - Automatic
other modes may
trAC - Tracking
bump.
(nor)

Configure Module 8 - Second Linear DC Analog Output (8-A2)

Controller returns to Configuration Access Point (CnFP-NO) if second
linear DC analog option is not installed.
Display
Parameter
A2tP
Second linear DC
output range
A2LO
Second linear DC
output low scaling
value
A2Hl
Second linear DC
output high scaling
value

Configure Module 9 - Factory Service Operations (9-FS)

Display
Parameter
CodE
Factory service
function code.
-27-
Range and Units
Description/
(Factory Setting)
Comments
0 to 10 V
Set Secondary
0 to 20 mA
Output jumper to
4 to 20 mA
match.
(4-20)
-999 to 9999
Corresponding temp
(0) CN63100
or process value for
(0.0) CN63300
low output.
-999 to 9999
Corresponding temp
(1000) CN63100
/ process value for
(100.0) CN63300
high output.
Range and Units
Description/
(Factory Setting)
Comments
48 - Calibrate
Refer to Calibration
instrument
Section for details.
66 - Reset
parameters to factory
settings
77- (twice in
succession) Reset
controller calibration
to nominal values
(Caution: This
operation results in
up to ±10% reading
error.)