Configure Module 5 - Cooling Parameters (5-O2)

Controller returns to configuration access point (CnFP NO) if Alarm 2 is
not configured as cooling output in Alarm Module (4-AL). Cooling output for
the CN63300 is referred to as the second control output.
Display
Parameter
CYC2
Cooling output cycle
time
GAN2
Relative cooling
gain
db-2
Heating or cooling
overlap/deadband
Range and Units
Description/
(Factory Setting)
Comments
0 to 250 sec
0 turns O2 off.
(2)
0.0 to 10.0
0.0 places cooling
(1.0)
output into ON/OFF
Control and db-2
becomes hysteresis
value.
-999 to 9999
Positive value is
(0)
deadband. Negative
value is overlap. If
GAN2 = 0, this
parameter is cooling
ON/OFF Control
hysteresis. Change
to Factory Setting
prior to Auto-Tune.
-25-