HIDDEN FUNCTION MODE

The Hidden Function Mode is only accessible from the Normal Display
Mode by pressing and holding the P button for three seconds. These
functions must first be unlocked in Configuration Module 3-LC. Factory
settings for these parameters is lock. In this mode, these controller functions
can be performed.
Remote/SP1/SP2 Setpoint Selection
Automatic/Manual Transfer
Initiate/Cancel Auto-tune
Reset Alarm Outputs
The P button is used to scroll to the desired function and the Up and Down
buttons are used to select the operation. Pressing the P button while the
function is displayed executes the function, and returns the unit to the Normal
Display Mode. Pressing the D button exits this mode with no action taken.
The unit automatically returns to the Normal Display Mode if no action is
taken within a few seconds.
Hidden Function Mode Reference Table
Range and Units
Display Parameter
(Factory Setting Value)
SPSL
Setpoint
SP1 - Setpoint 1
Select
SP2 - Setpoint 2
rSP - Remote Setpoint
trnF
Transfer
Auto - Automatic control
mode of
User - Manual control
operation
(Auto)
tUNE
Auto-tune
Yes: starts the
Invocation
auto-tune sequence.
No: terminates the
auto-tune sequence.
(NO)
ALrS
Alarm
UP button resets Alarm 1
Reset *
DOWN button resets
Alarm 2
* Model Number Dependent
Description/ Comments
Exits to Normal Display
Mode after being executed.
Exits to Normal Display
Mode after being executed.
Exits to Normal Display
Mode after being executed.
Does not exit to Normal
Display Mode after being
executed.
-19-

CONFIGURATION PARAMETER MODE

The Configuration Parameter Mode is accessed by pressing the Up button
from CnFP in the Unprotected Parameter Mode. While in this mode, the
various Configuration Modules can be displayed by pressing the Up or Down
buttons. The process value (after initial setup) will be displayed in the main
(top) display. The Configuration Module will appear alternating with CnFP
in the secondary (bottom) display.
To access a Configuration Module, press the P button when the desired
Configuration Module is displayed. The parameters of that Configuration
Module can be accessed by pressing the P button. (The module's parameters
are listed in the appropriate Configuration Module table in this section with
configuration parameter explanations beginning on page 30.) To modify
ranges and units, use the Up or Down arrows while the parameter is displayed.
The controller responds to the new values after the P button is pressed,
however, the change is not committed to permanent memory until the
controller is returned to the Normal Display Mode. If power loss occurred
before returning to the Normal Display Mode, the new values must be entered
again. Whenever the D button is pressed, End will momentarily appear and
the controller will return to the Normal Display Mode. At the end of each
module, the controller will go to CnFP no. Pressing the Up or Down arrows
will continue in Configuration Parameter Mode and pressing the P will return
to the Normal Display Mode.
Unless specified, the parameters, ranges, units and factory settings are the
same for CN63100 and CN63300 controllers. Parameters that are model
number or program dependent will only be displayed when the appropriate
options are installed or programmed. Some parameters are accessible but may
not be applicable for the chosen output control mode type.