Full Field Controller Transmission Byte Format - Omega CN63100 Series User Manual

1/16 din temperature/process controllers
Table of Contents

Advertisement

t
= (10 X # of characters) / baud rate
1
At the start of time interval t
, the controller starts the interpretation of the
2
command and when complete, performs the command function. This time
interval varies from 2 msec to 100 msec. If no response from the controller is
expected, the controller is ready to accept another command at the end of t
minimum delay of 100 msec for period t
another command to the same controller.
If the controller is to reply with data, the time interval t
use of the command terminating character. The standard command line
terminating character is '*'. This terminating character results in a response
time window of 100 msec minimum and 200 msec maximum. This allows
sufficient time for the release of the bus by the transmitter. Terminating the
command line with '$' results in a response time window (t
minimum and 100 msec maximum. The faster response time of this
terminating character requires that the transmitter release within 2 msec after
the terminating character is received.
At the beginning of time interval t
character of the reply. As with t
1
number of characters and baud rate of the channel.
t
= (10 X # of characters) / baud rate.
3
The number of response characters varies depending on the setting of the
full / abbreviated transmissions parameter. At the end of t
ready to receive the next command.
The maximum serial throughput of the controller is limited to the sum of:
t
, t
and t
.
1
2
3
must be observed before sending
2
is controlled by the
2
) of 2 msec
2
, the controller responds with the first
3
, the time duration of t
is dependent on the
3
, the controller is
3

Full Field Controller Transmission Byte Format

The first two characters transmitted are the node address, unless the node
address assigned = 0, in which case spaces are substituted. A space follows
the node address field. The next three characters are the register ID. The
numeric data is transmitted next. The numeric field is 5-6 characters long. If
. A
2
the decimal point is present, the field is 6 characters. Negative values have a
leading minus sign. The data field is right justified with leading spaces.
Engineering Units byte is next. The end of the response string is terminated
with a carriage return <CR> and line feed<LF>. When print block
transmission is finished, an extra <SP><CR><LF> is used to provide
separation between the blocks.
Byte
Description
1-2
2 byte Node Address field [00-99]
3
<SP> (Space)
4-6
3 byte Register ID field
7-12
6 byte data field, 4 bytes for number, one byte for sign, one byte
for decimal point
13
1 byte Engineering Units
14
<CR>
15
<LF>
16
<SP>(Space). This character only appears in the last line of a print
block.
17
<CR> This character only appears in the last line of a print block.
18
<LF> This character only appears in the last line of a print block.
-63-