Configure Module 3 - Lockout Parameters (3-LC)

Range and Units
Display
Parameter
(Factory Setting)
SP
Setpoint access
LOC - lockout
rED - read only
Ent - enter
(Ent)
OP
Output power
LOC - lockout
access
rED - read only
Ent - enter
(Ent)
dEv
Deviation display
LOC - lockout
access
rEd - read only
(rEd)
UdSP
Units display
LOC - lockout
access
rEd - read only
For CN63100
(rEd)
bdSP
Blank display
LOC - lockout
access
rEd - read only
For CN63300
(rEd)
CodE
Access code
0 to 250
(0)
Description/ Comments
Determines access to
temperature setpoint.
Determines direct
access to output power.
%P indicator illuminates
when parameter is
selected in display.
Determines display of
deviation. DV indicator
illuminates when
parameter is selected in
display.
Determines display of F
or C.
Determines blank
secondary display.
Refer to front panel
disable section for
access levels.
-23-
Range and Units
Display
Parameter
(Factory Setting)
PId
PID values
LOC - lockout
access
rEd - read only
Ent - enter
(LOC)
AL
Alarm values
LOC - lockout
enable *
rEd - read only
Ent - enter
(LOC)
ALrS
Reset alarms
LOC - lockout
enable *
ENBL - enable
(LOC)
SPSL
SP1/SP2/Remote
LOC- lockout
setpoint enable *
ENBL - enable
(LOC)
trnF
Automatic/Manual
LOC - lockout
(user) mode
ENBL - enable
select enable
(LOC)
tUNE
Auto-tune enable LOC- lockout
ENBL - enable
(LOC)
* Model Number Dependent
Description/ Comments
Protected Mode lockout.
Protected Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.
Hidden Mode lockout.