Configure Module 4 - Alarm Parameters (4-AL)

Controller returns to configuration access point (CnFP NO) if alarm(s) are
not installed.
Display
Parameter
ACt1
Alarm 1 action
A-HI - absolute high
mode
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
Heat - control output *
(A-HI)(HEAt) *
rSt1
Alarm 1 reset
Auto - automatic
mode
LAtc - manual reset
(Auto)
Stb1
Alarm 1 standby
yes/no
function (delay)
(no)
AL-1
Alarm 1 value
-999 to 9999
(0) CN63100
(0.0) CN63300
ACt2
Alarm 2 action
A-HI - absolute high
mode *
A-LO - absolute low
d-HI - deviation high
d-LO - deviation low
b-IN - band inside
b-ot - band outside
CooL- cooling output
(A-HI)
Range and Units
Description/
(Factory Setting)
Comments
If changed, check
alarm values. If heat
is selected, the
remaining alarm
parameters do not
appear. For
CN63300, heat is
main control output.
Manual reset via
Hidden Mode or user
input.
Power-up standby
delay.
If band alarm action,
then only a positive
value can be
entered.
If changed, check
alarm values. If
cooling is selected,
the remaining Alarm
2 parameters do not
appear.
For CN63300, cool is
second PID control
output.
Display
Parameter
rSt2
Alarm 2 reset
mode *
Stb2
Alarm 2 standby
function (delay) *
AL-2
Alarm 2 value *
AHYS
Alarm Hysteresis
value
* Model Number or Mode Setting Dependent
-24-
Range and Units
Description/
(Factory Setting)
Comments
Auto - automatic
Manual reset via
LAtc - manual reset
hidden Mode or user
(Auto)
input.
yes/no
Power-up standby
(no)
delay.
-999 to 9999
If band alarm action,
(0) CN63100
then only a positive
(0.0) CN63300
value can be
entered.
1 to 250
Applies to both
(1) CN63100
alarms. Set to
(0.1) CN63300
eliminate chatter.