LINEAR DC ANALOG OUTPUT JUMPER SELECTION
(Main & Second)
The Linear Analog DC Output ranges are selectable for either voltage
(0-10 V) or current (0/4-20 mA). The main set of jumpers must correspond
with the configuration in Linear Output Range (ANAS) in the Output
Parameter Module (2-OP). The optional secondary set of jumpers must
correspond with the configuration in Second Linear DC Output Range (A2tP)
in the Second Linear DC Analog Output Module (8-A2). The jumpers are
accessible from the rear after removing the controller from the case. Dashed
lines show factory setting of 20 mA.
Figure 10, Linear Output Range Jumpers
-11-