Residential Installation Instructions - Osburn 2200 Owner's Manual

Us environmental protection agency phase ii certified woodstove
Hide thumbs Also See for 2200:
Table of Contents

Advertisement

1.3

Residential Installation Instructions

Choose a location for the unit which meets the minimum clearances to combustibles (see Table 1.1). For
other than masonry chimneys determine if the factory built chimney will pass between the ceiling joists; if
not, choose a new location so that it will, while still maintaining the minimum clearances.
1. Mark the location for the floor protection
(if required) as noted in Figure 1.1.
Note: If outside air for combustion is to be used it should be provided for at this time. This requires that the
Osburn Fresh Air Kit Wood (#OA10500) be installed (refer to the installation instructions which are
provided in the outside air kit. Install the unit.
Floor Protection Requirements (for combustible floors)
If the stove is to be installed on top of a combustible floor it must be guarded by a non-combustible
material extending beneath the heater and to the front and sides as indicated in Figure 1.1, or to the nearest
permitted combustible material. Floor protection must extend beneath, and 2" (51 mm) to the sides of a
horizontal connector if one has been used.
Please note that floor protection is required for spark and ash shielding, but not for limiting floor
temperatures from the radiant heat of the stove. The stove was designed and safety tested so that without
any protection the floor would not overheat even under over firing conditions. Please refer to local codes
for suitable floor protection materials.