CONFIGURATION PROGRAM

This is a new feature included with the new UPStation GXT 2U line. Sev-
eral UPS settings that were previously not available or required custom
manufacturing may now be modified using this program. For most users,
the factory default settings will be adequate. This manual illustrates the
features available for modification, as well as the factory default setting.
GXT 2U C
ONFIGURATION
Select one of five output voltages to match voltages found around
the world.
Enable/Disable Auto-Restart.
Enable/Disable the Line-Neutral-Reversal/Loss-of-Ground recepta-
cle wiring alarm.
Select frequency converter operation with a fixed output frequency
of 50 or 60 Hz.
Set the Low Battery Warning alarm time from 2 to 30 minutes.
Enable/Disable the Auto-Battery test.
Set the Auto-Battery test to 7, 14, 21, or 28 days.
Select the number of external battery cabinets connected to the
UPS to adjust the remaining run time calculations reported by Lie-
bert software products.
NOTE
This program is compatible with UPS models beginning with
"GXT2-", as in "GXT2-1500RT120". It is not compatible with
earlier versions of UPStation GXT UPS.

What You Will Need

In addition to the GXT 2U UPS, you will need the configuration program
diskette and serial cable (Beige or Tan, 3-wire: GND, TX, RX; straight
through 2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK
ML9P9S CONTACT CLOSURE communication cable IS NOT compatible
with the configuration program. A Windows 95
desktop or laptop—is also required to set up and run the configuration
program.
P
A
ROGRAM
BILITIES
19
®
®
®
, 98
, or NT
computer—