SPECIFICATIONS (CONTINUED)
Model Number
Model Rating
DIMENSIONS in (mm)
Unit
W x D x H in. (mm)
Shipping
W x D x H in. (mm)
WEIGHT lbs (kg)
Unit
Shipping
INPUT AC PARAMETERS
Voltage Range
(typical)
100% - 90% loading
90% -70% loading
70% -30% loading
30% - 0% loading
Frequency
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
Voltage
Frequency
Waveform
Main Mode
Overload
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Mfg / Part #
Back-up Time
Recharge Time
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
RFI/EMI
Surge Immunity
Transportation
GXT2-2000RT120
2000VA / 1400W
3.5 x 21.5 x 17
(87 x 547 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
54 (24)
62.6 (28.4)
120 VAC nominal; variable based on output load
90 VAC / 140 VAC
80 VAC / 140 VAC
70 VAC / 140 VAC
60 VAC / 140 VAC
10 ft. attached
w/ NEMA 5-20 plug
(4) 5-20R T-Slot,
accepts 15A plug
100/110/115/120/127 (user configurable) VAC; ±3%
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, flame retardant, lead acid
4 x 12V x 9.0 AH
Panasonic / UP-VW1245P1
See Battery Run Times charts
5 hours to 95% capacity after full discharge into 100% load
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000 m) maximum
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
UL 1778, c-UL Listed (Suitable for computer room applications)
FCC Part 15, Subpart B, Class A
IEEE/ANSI C62.41 Category A & B
40 - 70 Hz; Auto Sensing
(1) NEMA L5-30R on 12 in cord
50 Hz or 60 Hz
Sinewave
Yuasa / REW 45-12 FR
ISTA Procedure 1A
29
GXT2-3000RT120
3000VA / 2100W
3.5 x 24.2 x 17
(87 x 618 x 430)
10.5 x 27.2 x 23
(268 x 692 x 585)
69 (31)
78.0 (35.4)
90 VAC / 140 VAC
80 VAC / 140 VAC
70 VAC / 140 VAC
60 VAC / 140 VAC
10 ft. attached
w/ NEMA L5-30 plug
(4) NEMA 5-15R
6 x 12V x 9.0 AH