Heat & Glo SL-350TRS-CE-D Installer's Manual page 29

Hearth & home technologies gas fireplace installation manual
Hide thumbs Also See for SL-350TRS-CE-D:
Table of Contents

Advertisement

NOTE
WARNING:
!
FOLLOW NATIONAL REGULATIONS
AND CODES OF PRACTICE FOR
MINIMUM CLEARANCES FROM GAS
TERMINALS, AND PLACEMENT OF GAS
TERMINAL.
This also pertains to vertical flue systems installed
on the outside of the building.
TERMINATION
CAP
61 cm
51 cm
(For DVP Series)
LOWEST
DISCHARGE
TERMINATION
OPENING
CAP
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Roof Pitch
flat to 6/12
6/12 to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
* 91.4 cm minimum in snow regions
Figure 36. Minimum Height from Roof to Lowest
Discharge Opening
Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. N • 10/07
VERTICAL
WALL
X
30.5 cm
ROOF PITCH
IS X/ 30.5 cm
H (min.) cm
30.5*
38*
45.75*
61*
76.25*
99
122
152.5
183
213.5
228.75
244