7.1.2

Audible Alarm

An audible alarm will be used in conjunction with the visual indicators to indicate to the user a
change in UPS operating status. The audible alarm will enunciate as given in Table 8.
Table 8
Audible alarm description
Battery discharge
Low battery
UPS fault, load on bypass
UPS fault, no power to load
Overload
Battery replacement
Battery loss
Wiring problem (including line-to-neutral reversal
or a loss of proper grounding for UPS)
Bypass reminder
7.2

Troubleshooting

In the event of an issue with the UPS, refer to Table 9 to determine the cause and solution. If the
issue persists, contact Emerson Channel Support.
Table 9
Troubleshooting
Problem
UPS fails to start when the
On/Alarm Silence/Manual
Battery Test button is pressed
Battery indicator is illuminated
UPS has reduced battery
backup time
Fault and Bypass indicators and
all LED segments of battery
level indicator are illuminated
Fault and Bypass indicators and
diagnostic A indicator are
illuminated
Condition
Cause
UPS is short-circuited or overloaded
UPS not plugged in
UPS input protection fuse has
blown/opened
Utility power is out of tolerance
Batteries are not fully charged
UPS is overloaded
Batteries may not be able to hold a
full charge due to age
UPS overloaded or load is faulty
UPS shutdown due to temperature
condition. Load is on bypass power
Alarm
half-second beep every 10 seconds
Two half-second beeps every 5 seconds
1-second beep every 4 seconds
Continuous
half-second beep every half second
2-second beep every 60 seconds
Continuous
Continuous
1-second beep every 2 minutes
Ensure UPS is Off. Disconnect all loads and
ensure nothing is lodged in output receptacles.
Ensure loads are not defective or shorted
internally
UPS is operating from battery mode, ensure
UPS is securely plugged into the wall receptacle
UPS is operating from battery mode. Save data
and close applications. Replace UPS input fuse,
then restart UPS
UPS is operating from battery mode. Save data
and close applications. Ensure utility supply
voltage is within acceptable limits for UPS
Keep UPS plugged in continuously at least 24
hours to recharge batteries
Check load level indicator and reduce the load
on the UPS
Replace batteries. Contact your local dealer,
Emerson representative or Emerson Channel
Support for replacement battery kit
Check load level indicator and remove non-
essential loads. Recalculate the load and reduce
number of loads connected to UPS. Check load
for faults
Ensure UPS is not overloaded, ventilation holes
not blocked, or room ambient temperature is not
excessive. Wait 30 minutes to allow UPS to cool,
then restart UPS. If UPS cannot restart, contact
your local dealer, Emerson representative or
Emerson Channel Support.
32
Troubleshooting