Audible Alarm (Buzzer); Control Keys - Emerson Liebert APM 90 User Manual

Integrated modular
Table of Contents

Advertisement

Indicator
Rectifier indicator
Battery indicator
Bypass indicator
Inverter indicator
Load indicator
Status indicator

4.1.2 Audible Alarm (Buzzer)

UPS activity is accompanied by the two kinds of sound listed in Table 4-3.
Beep every other second
Continuous beep

4.1.3 Control Keys

The operator control and display panel provides five control keys, as described in Table 4-4.
Control key
EPO switch
Inverter start switch
Inverter shutdown
switch
Fault reset switch
Audible alarm
silencing switch
Table 4-2 Indicator description
State
Solid green
Rectifiers in normal operation
Flashing green
Mains input normal, but rectifiers not operating
Solid red
Rectifiers failed
Off
Rectifiers not operating, mains input abnormal
Solid green
Load on battery
Flashing green
Battery EOD pre-warning
Battery abnormal (failed, absent or polarity reversed) or battery
Solid red
converter abnormal (failed, overcurrent or overtemperature)
Off
Battery and battery converter normal, battery charging
Solid green
Load on bypass
Bypass power abnormal or outside specifications, or static bypass switch
Solid red
fault
Off
Bypass normal
Solid green
Load on inverters
Inverters turning on, starting up, synchronizing, or standing by (ECO
Flashing green
mode)
Solid red
Inverter fault
Off
Inverters not operating
Solid green
UPS output on and normal
Solid red
UPS output on and overloaded
Off
UP output off
Solid green
Normal operation
Solid yellow
Alarm (for example, AC input failure)
Solid red
Fault (for example, fuse or hardware fault)
Table 4-3 Audible alarm description
Alarm sound
Table 4-4 Description of control keys
Silkscreen
Cut off the load power, shut down the rectifier, inverter, static bypass
EPO
and battery
INVERTER ON
Start the inverter
INVERTER OFF
Shut down the inverter
FAULT CLEAR
Restart the UPS (subject to any fault being cleared)
When an alarm is active, pressing this button silences the audible alarm.
SILENCE ON/OFF
Pressing this button again enables the buzzer again
Liebert APM 90 Integrated Modular UPS User Manual
Chapter 4 Operator Control And Display Panel
Description
Meaning
UPS alarm, for example, AC input failure
UPS fault, for example, fuse or hardware fault
Description
27