Installation; Unpacking And Inspection; What's Included; Preparation For Installation - Emerson Liebert GXT3 Series User Manual

Ups 120v/208v 500va-3000va
Hide thumbs Also See for Liebert GXT3 Series:
Table of Contents

Advertisement

2.0
I
NSTALLATION
2.1

Unpacking and Inspection

Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and
your local dealer or your Emerson representative immediately.
• Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Emerson representative immediately.
2.2

What's Included

With GXT3 UPS
• Compact Disk with:
• Liebert MultiLink
• Configuration Program
• User Manual
• USB Cable: one, 6-1/2 ft. (2m) long
• Mounting hardware, including screws and handles
• Plastic tower stand sets: 2 (four pieces)
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE
The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
spacers for tower configuration and one DC power cable.
2.3

Preparation for Installation

2.3.1

Installation Environment

• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.
The installation environment should meet the specifications listed in 9.0 - Specifications).
• Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids,
gases, corrosives, and conductive contaminants. Avoid direct sunlight.
NOTE
Operating the Liebert GXT3 in temperatures above 77°F (25°C) reduces battery life.
Installation Clearances
Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not
obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
2.4

Mechanical Installation

The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use consider-
ations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery cabinets.
NOTE
When installing the UPS or making input and output connections, comply with all relevant
safety codes and standards
11

Installation