Audible Alarm

An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS
operating status. The audible alarm will sound as described in Table 12.
Table 12
Audible alarm description
Condition
Battery discharge
Low battery
UPS fault, load on bypass
UPS fault, no power to load
Overload
Battery replacement
Battery loss
Wiring problem (loss of proper grounding for UPS)
Bypass reminder
7.2

Troubleshooting

In the event of an issue with the UPS, refer to Table 13 to determine the cause and solution. If the
fault persists, contact Emerson
Table 13
Troubleshooting table
Problem
UPS fails to start
Battery indicator is illuminated
UPS has reduced battery
backup time
Battery indicator is flashing.
Bypass indicator is flashing.
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are
located in several places for your ease of location: on the top panel (rack mount orientation); the left
side (tower orientation); the rear panel; on the front of the unit behind the front plastic bezel; and on
the LCD select Main Menu > About.
Half-second beep every 10 seconds
Two half-second beeps every 5 seconds
1-second beep every 4 seconds
Continuous
Half-second beep every half second
2-second beep every 2 minutes
Continuous
Continuous
1-second beep every 60 seconds
®
Channel Support.
Cause
UPS is short-circuited or
overloaded
Batteries are not charged
enough or not connected
UPS is not plugged in
UPS input protection fuse has
blown/opened
Mains power is out of tolerance
Batteries are not fully charged
UPS is overloaded
Batteries may not be able to
hold a full charge due to age
Battery source is not available;
continuous horn.
Because the voltage or
frequency is outside acceptable
limits, the bypass is disabled.
Alarm
Ensure UPS is Off. Disconnect all loads and ensure
nothing is lodged in output receptacles. Ensure loads are
not defective or shorted internally.
Check to ensure the internal battery is connected. If it is
not, make the connection and try to start the unit. If the
battery is connected, leave the UPS connected to input
power for 24 hours to recharge batteries, then try to start
the unit.
UPS is operating from battery mode. Ensure UPS is
securely plugged into the wall receptacle.
UPS is operating from battery mode. Save data and close
applications. Replace UPS input fuse, then restart UPS.
UPS is operating from battery mode. Save data and close
applications. Ensure mains supply voltage is within
acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to
recharge batteries.
Check load level indicator and reduce the load on the
UPS.
Replace batteries. Contact your local dealer, Emerson
representative or Emerson Channel Support for
replacement battery kit.
Check battery connections, completely power down and
restart UPS.
NOTE: If the battery circuit opens while the UPS is
running, it will be detected when the next battery test is
performed.
The AC input powers the PFC input and serves as the
bypass source. If the AC is present but the voltage or
frequency exceeds the acceptable range for safe
operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is
unavailable.
49
Troubleshooting
Solution
®
Liebert
GXT4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents