6.0
M
AINTENANCE
This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3's
status and checking UPS functions.
6.1

Replacing the Internal Battery Pack

The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Read the
safety cautions before proceeding. Contact your local dealer or Emerson representative to obtain the
part number and pricing of the appropriate replacement battery pack.
6.1.1

Battery Replacement Procedures

1. Remove the front plastic bezel cover from the UPS.
2. Loosen and remove the six screws on the battery door, as shown in Figure 22.
3. Lay the battery door and screws aside for reassembly.

Figure 22 Removing the front bezel cover and battery door

Battery Door
Screws, 6
Front Bezel
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown
in Figure 23.

Figure 23 Disconnecting the battery plug and battery receptacle (front view)

Battery Connector
5. Grasp the battery handle, and pull the internal battery pack out of the UPS, as shown in
Figure 24.
Battery Receptacle