Grounding The Switch; Cable Installation - Mellanox Technologies SwitchX MSX1016X-2BFR Hardware User Manual

Switchx 64 port sfp+ ethernet switch
Table of Contents

Advertisement

SwitchX® 64 Port SFP+ Ethernet Switch Hardware User Manual
Caution: The power supplies in this switch are Double Pole / Neutral Fusing.
Caution: The switch platform will automatically power on when AC power is applied.
There is no power switch. Check all boards, power supplies, and fan tray modules for
proper insertion before plugging in a power cable.
Caution: After inserting a power cable and confirming the green system status LED
light is on; make sure that the Fan Status indicator shows green.
If the fan status indicator is not green then unplug the power connection and check that
the fan module is inserted properly and that the mating connector of the fan unit is free
of any dirt and/or obstacles.
Caution: When turning off the switch, make sure ALL Connector LEDS are off to
ensure a powered down status.
4.1.3

Grounding the Switch

Check to determine if your local or national electrical codes require an external ground to all IT
components. If so, connect a ground wire to one of the casing screws and connect the other end to
a valid ground. If you choose to not use the ground screw, make sure that the rack is properly
grounded and that there is a valid ground connection between the chassis of the switch and the
rack. Test the ground using an Ohm meter.
Some national and/or local codes may require IT components to be bonded and exter-
nally grounded (not including the power cord ground). You must follow all national
and local codes when installing this equipment.
4.1.4

Cable Installation

All cables can be inserted or removed with the unit powered on. To insert a cable, press the con-
nector into the port receptacle until the connector is firmly seated. The orange LED indicator cor-
responding to each port will light when the physical connection is established (that is, when the
unit is powered on and a cable is plugged into the port with the other end of the connector
plugged into a functioning port). After plugging in a cable, lock the connector using the latching