Powerware 9170 User Manual page 83

3kva-18kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Table 14. Environmental and Safety
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Non-Operating Altitude
Ventilation
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
Table 15. Battery
Configuration
Voltage
Type
Charging
Powerware
9170 User's Guide
®
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
UPS with battery modules: –20°C to +40°C (–4°F to 104°F)
UPS without batteries: –40°C to +60°C (–40°F to 140°F)
5–95% noncondensing
Up to 3,050 meters above sea level (10,000 ft)
The maximum operating ambient temperature decreases 1°C per 300m above 1525m
(2°F per 1000 ft above 5000 ft)
Up to 12,200 meters above sea level (40,000 ft)
The air around the UPS must be clean and free of dust, corrosive chemicals, and other
contaminants. The Powerware 9170 UPS uses internal fans to circulate the air for cooling.
The air must be free to circulate around the UPS and battery cabinet(s). Do not operate the
UPS in a sealed room or container.
Less than 53 dBA
ANSI C62.41 Category B (formerly IEEE 587); IEC 61000-4-5
CAN/CSA C22.2, No. 107.1; UL 1778;
EN 50091-1-1 and IEC 60950
UL, cUL, TÜV, CE, C-Tick, BCIQ
EN 50091-2, FCC Part 15, ICES-003, VCCI
(2) 60V, 7.2 Ah batteries per string
120 Vdc
Sealed, maintenance-free, valve-regulated, lead-acid
Recharge time: 4 hr after full-load resistive discharge; 8 hr after half-load resistive
discharge, using standard internal battery charger.
Optional battery chargers at higher current ratings will be available for future product
release.
:
www.powerware.com
Specifications