Electrical Installation
Table 3. Bypass Switch Positions
Switch Position
LINE
Connects the load directly to AC input power and disconnects UPS output. AC input power is still
connected to the UPS input.
OFF
Disconnects the load from the UPS output power and AC input power, as well as AC input power
to the UPS input.
UPS
Connects the UPS output to the load.
SERVICE
Like the LINE position, SERVICE connects the load directly to AC input power and disconnects
UPS output. However, because SERVICE also disconnects AC input from the UPS, this is
the appropriate position for UPS maintenance or repair.
To disconnect AC input power during maintenance or service, turn the
bypass switch to the SERVICE position. For MBB switches, you must
press the red button beside the switch before you can change the switch
position.
There are six bypass switch models available for the Powerware 9170
UPS as specified in Table 4.
Table 4. Bypass Switch Specifications
Bypass Switch Models
BBM
MBB
BPE12BBM1A
BPE12MBB1A
BPE14BBM1A
BPE14MBB1A
BPE22BBM1A
BPE22MBB1A
28
R ti
Rating,
Height
Continuous
Continuous
(A)
2
40A/300 Vac
21.0
(CSA)
(534 mm)
50A/300 Vac
(UL,TÜV)
2
80A/300 Vac
21.0
(534 mm)
2
150A/300 Vac
26.5
(673 mm)
Description
See Figure 20
Width
Depth
Mounting Centers
(B)
(C)
(D)
2
2
14.0
6.8
11.0
(356 mm)
(172 mm)
(280 mm)
2
2
14.0
6.8
11.0
(356 mm)
(172 mm)
(280 mm)
2
2
18.4
6.6
16.0
(467 mm)
(168 mm)
(406 mm)
Powerware
9170 User's Guide
®
Weight
(E)
2
2
20.0
27 lb
(508 mm)
(12.3 kg)
2
2
20.0
31 lb
(508 mm)
(14.1 kg)
2
2
25.5
53 lb
(648 mm)
(24.1 kg)
:
www.powerware.com