Powerware 9170 User Manual page 82

3kva-18kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Specifications
Table 12. Isolation
Model 0650C Output
Neutral-to-Ground Bonding
Model 0650I Isolation, Including
Output Neutral-to-Ground
Bonding
Table 13. Model Specifications
kVA
Watts
Input Current for
208/220/230/240V*
3
2100
17/16/15/15A
6
4200
31/29/28/27A
9
6300
46/44/42/41A
12
8400
62/59/56/53A
15
10500
77/73/70/67A
18
12600
93/87/84/80A
kVA
Watts
Input Current
for 200V*
3
2100
18A
6
4200
32A
9
6300
48A
12
8400
64A
15
10500
80A
18
12600
100A
*For redundant power module operation (N+X), increase the input current rating by 2A for each additional redundant power
module.
78
±3% load regulation (under any line, load, or battery condition)
Neutral is carried through from input to output; a separate neutral-to-ground bond is
not required
True, separately-derived power source as defined by National Electrical Code
Article 250-5d, with output neutral bonded to ground. No direct connection between
input and output; neutral-to-ground bond is required; other local codes may take
precedence.
Output Current for
208/220/230/240V
14.4/13.6/13.0/12.5A
28.8/27.2/26.0/25.0A
43.2/40.8/39.0/37.5A
57.6/54.4/52.0/50.0A
72.0/68.0/65.0/62.5A
86.4/81.6/78.0/75.0A
Voltages Only Available with Split-Phase Modules
Output Current for
100/200V, 110/220V, 120/240V
30/15A, 27/14A, 25/12.5A
60/30A, 54/28A, 50/25A
90/45A, 81/42A, 75/37.5A
120/60A, 108/56A, 100/50A
150/75A, 135/70A, 125/62A
180/90A, 162/84A, 150/75A
Recommended
Heat Dissipation
Input Service*
Double-Conversion Mode
25A
285W (0.98 kBTU/hr)
40A
570W (1.95 kBTU/hr)
60A
860W (2.93 kBTU/hr)
80A
1145W (3.90 kBTU/hr)
100A
1430W (4.88 kBTU/hr)
125A
1720W (5.85 kBTU/hr)
Recommended
Heat Dissipation
Input Service*
Double-Conversion Mode
25A
285W (0.98 kBTU/hr)
40A
570W (1.95 kBTU/hr)
60A
860W (2.93 kBTU/hr)
80A
1145W (3.90 kBTU/hr)
100A
1430W (4.88 kBTU/hr)
125A
1720W (5.85 kBTU/hr)