Specifications

Protection Features

Battery reverse
polarity
Over-voltage limits
Output current limit TC1012:
Over-temperature
Current derating in
ambient
temperatures
Battery over-
temperature
protection
Battery under-
temperature
protection
A–6
Protected by replaceable DC output fuses
The Truecharge™ 2 Battery Charger will stop
charging if the output voltage is above
16.6 ±0.5 Vdc.
10 +10% A
TC1512:
15 +10% A
TC2012:
20 +10% A
TC3012:
30 +10% A
TC4012:
40 +10% A
TC5012:
50 +10% A
TC6012:
60 +10% A
TC1524:
15 +10% A
TC2024:
20 +10% A
TC3024:
30 +10% A
TC5024:
50 +10% A
Internal charger temperature is measured. Charger
shuts down and restarts as follows:
Shutdown at 70 °C (158 °F)
Restart at 60 °C (140 °F)
See "Environmental Specifications" on page A–5.
Charger shuts down if battery temperature above
70 °C (158 °F) is sensed by the battery temperature
sensor.
Charger shuts down if battery temperature below
–25 °C (–13 °F) is sensed by the battery temperature
sensor.